Install Manual
Table Of Contents
Control Panel Startup/Testing
40 Installation Guidelines for 60 Hz Air-Cooled Generators
7. Verify fuel pressure while cranking. Record crank-
ing fuel pressure:________
8. Allow  engine  to  stabilize  and  warm  up  for  a  few
minutes.
9. Verify fuel pressure while running. Record running
fuel pressure:________
10. Set  generator  main  line  circuit  breaker  (generator
disconnect) to ON (CLOSED). Loads are now pow-
ered by standby generator.
11. Turn on circuit breakers/electrical loads to be pow-
ered by generator one by one.
12. Connect a calibrated AC voltmeter and a frequency
meter  across  terminal  lugs  E1  and  E2.  Voltage
should  be  approximately  240  volts  and  frequency
should be approximately 60 Hz. If voltage and fre-
quency are  rapidly dropping as loads are applied,
generator may be overloading,  or  there may be a
fuel  issue.  Check  output  current  measurement  of
loads and/or fuel pressure.
13. Allow generator to run at full rated load for 20–30
minutes.  Listen  for  unusual  noises,  vibration,  or
other indications of abnormal operation. Inspect for
oil leaks, evidence of overheating, etc.
14. Verify  fuel  pressure  while  under  full  load.  Record
loaded fuel pressure: ______________.
15. Turn off electrical loads when testing under load is
complete.
16. Set  generator  main  line  circuit  breaker  (generator
disconnect) to OFF (OPEN).
17. Allow engine to run at no-load for 2–5 minutes.
18. Press generator OFF mode button. The engine will
shut down.
NOTE: If fuel pressure under full load is below minimum
operating  fuel  pressure  guideline,  generator  may  not
function correctly. The fuel pressure gauge needle should
also remain steady while testing. A fluctuating fuel pres-
sure  gauge  needle  indicates  gas  piping  may  be  under-
sized or restricted. It may also indicate a step-down gas
regulator is too small, or too close to the unit. 
Checking Automatic Operation
Proceed as follows to check system for correct automatic
operation:
1. Verify generator is OFF.
2. Install front cover of transfer switch.
3. Turn on utility power supply to transfer switch using
the means provided (such as a utility MLCB).
NOTE: Transfer switch will transfer to utility position.
4. Set  generator  main  line  circuit  breaker  (generator
disconnect) to ON (CLOSED).
5. Press generator AUTO button. The system is now
ready for automatic operation.
6. Turn OFF utility power supply to transfer switch.
The  generator  is  ready  for  automatic  operation.  The
engine  will  crank  and  start  when  utility  source  power  is
turned off after a  five  second  delay  (factory  default  set-
ting). After starting, transfer  switch  will connect load cir-
cuits  to  the  standby  side  after  a  5  or  30  second  delay
(dealer  programmable).  See  Cold Smart Start.  Allow
system to operate through entire automatic sequence of
operation.
With generator running and loads powered by generator
AC output, turn on utility power supply to transfer switch.
The following will occur:
• After  approximately  15  seconds  (dealer  program-
mable),  the  switch  will  transfer  loads  to  the  utility
power source.
• Approximately one minute after transfer, engine will
shut down.
Installation Summary
1. Verify installation has been performed correctly as
outlined by the manufacturer and  that  it  meets  all
applicable laws and codes.
2. Test and verify correct operation of the system as
outlined in the appropriate installation and owner’s
manuals.
3. Educate  end-user  on  correct  operation,  mainte-
nance, and service call procedures. 
Shutting Generator Down While 
Under Load or During a Utility Outage
IMPORTANT NOTE: To avoid equipment damage, fol-
low these steps, in order, during utility outages. Shut-
downs may be required during utility outages to perform 
routine maintenance or to conserve fuel.
To turn generator OFF:
1. Set main utility disconnect to OFF (OPEN).
2. Set  generator  MLCB  (generator  disconnect)  to
OFF (OPEN).
3. Allow  generator  to  run  for  cool-down  for  approxi-
mately one minute.
4. Set generator to OFF at the controller.
5. Remove 7.5A fuse from controller.
To turn generator back ON:
1. Install 7.5A fuse in controller.
Automatic start-up. Disconnect utility power and 
render unit inoperable before working on unit. 
Failure to do so will result in death or serious injury.
(000191)
DANGER










