Install Manual
Table Of Contents
Fuel Conversion / Gas Connections
Installation Guidelines for 60 Hz Air-Cooled Generators 23
Natural Gas Pipe Sizing
To determine correct NG pipe size, find the kW rating of
generator in the left column,  and  trace  to  the  right. The
number to the right is maximum length (measured in ft /
m) allowed for the pipe sizes on top. Pipe sizes are mea-
sured  by  trade  size  diameter  to  include  any  fittings,
valves (must be full flow), elbows, tees, or angles. 
NOTE: See Table B.3.2 in NFPA 54 or Table A.2.2 in the
ICC  IFGC,  Equivalent  Lengths  of  Pipe  Fittings  and
Valves for the correct values to be added to overall fuel
piping  length.  Tables  are  based  on  schedule  40  black
pipe. If installing any other piping system, follow pipe siz-
ing charts for selected piping system.
LP Gas Pipe Sizing
To determine correct LP gas pipe size, find the kW rating
of generator in the left column, and trace to the right. The
number to the right is maximum length (measured in ft /
m)  allowed  for  pipe  sizes  on  top.  Pipe  sizes  are  mea-
sured  by  trade  size  diameter  to  include  any  fittings,
valves  (must  be  full  flow),  elbows,  tees,  or  angles.  See
Table B.3.2 in NFPA 54 or Table A.2.2 in the ICC IFGC,
Equivalent  Lengths  of  Pipe  Fittings  and  Valves  for  the
correct values to be added to overall fuel piping length.
NOTE:  Pipe  sizes  are  from  the  outlet  of  the  second
stage  regulator  to  the  fuel  shutoff valve. Table is  based
on schedule 40 black pipe. If installing any other piping
system, follow the pipe size charts for the selected piping
system.
NOTE: Recommended minimum LP tank size is 250 gal
(946 L). Contact LP provider to correctly size LP tank to
generator. Vertical tanks, which are measured in pounds
(or kilograms), are permitted if correctly sized for the gen-
erator.  Do  not  connect  generator  to  a  20  or  30  lbs  LP
tank.
Table 5-1. NG Pipe Sizing
Pipe Size 
(in / mm)
For 5–7 in Water Column
(1.24–1.74 kPa)
For 3.5–5 in Water Column
(0.87–1.24 kPa)
Allowable Pipe Distances (ft / m)
0.5 / 13 0.75 / 19 1 / 25 1.25 / 32 1.5 / 38 0.75 / 19 1 / 25 1.25 / 32 1.5 / 38
9 kW 10 / 3.1 60 / 18.3 200 / 61 750 / 228.6 — 20 / 6.1 60 / 18.3 175 / 53.3—
11 kW — 30 / 9.1 100 / 3.5 450 / 137.2 — — 30 / 9.1 125 / 38.1 200 / 61
16–20 kW — 10 / 3.1 35 / 10.7 140 / 42.3 300 / 91.4 — 10 / 3.1 60 / 18.3 125 / 38.1
22 kW — 10 / 3.1 30 / 9.1 115 / 35.1 250 / 76.2 — 10 / 3.1 60 / 18.3 125 / 38.1
Table 5-2. LP Gas Pipe Sizing
Pipe Size (in / mm)
For 10–12 in Water Column 
(2.49–2.99 kPa)
Allowable Pipe Distances (ft / m)
0.5 / 13 0.75 / 19 1 / 25 1.25 / 32
9 kW 35 / 10.7 175 / 53.3 600 / 182.9 —
11 kW 15 / 4.6 80 / 24.4 350 / 106.7 —
16-22 kW — 40 / 12.2 175 / 53.3 550 / 167.6










