Install Manual
Table Of Contents
Site Selection and Preparation
Installation Guidelines for 60 Hz Air-Cooled Generators 17
Fresh Air for Ventilation and Cooling
Install  unit  where  air  inlet  and  outlet  openings  will  not
become  obstructed  by  leaves,  grass,  snow,  etc.  If
prevailing  winds  will  cause  blowing  or  drifting,  consider
using a windbreak at a safe distance to protect the unit.
Water Ingress Avoidance
• Select a location on high ground where water lev-
els  will  not  rise  and  flood  the  generator. This  unit
should not operate in, or be subjected to, standing
water.
• Install unit where rain gutter downspouts, roof run-
off, landscape irrigation, water sprinklers, or sump
pump discharge does not flood unit or spray enclo-
sure, including any air inlet or outlet openings.
• Excess moisture can cause  excess corrosion and
decrease life expectancy of the unit.
Proximity to Utilities
• Contact  local  utility  providers  and  verify  proposed
site  selection  meets  all  required  utility  placement
requirements  before  installation.  This  could  affect
warranty coverage.
• Remember,  laws  and  or  codes  may  regulate  dis-
tance and location of unit to specific utilities.
• It  is  recommended  to  pick  a  location  where  the
generator  is  as  close  as  possible  to  the  transfer
switch and the  fuel supply, while verifying the site
location conforms to the rest of the Site Selection
section.
Verify Wi-Fi Range
See Wi-Fi manual shipped with the unit if planning to use
the Wi-Fi feature.
Transportation Recommendations
Use  a  suitable  cart  or  equipment  to  carry  generator,
including  wooden  pallet,  to  installation  site.  Place
cardboard  between  cart  and  generator  to  prevent  any
damage or scratches to generator.
Do not lift, carry, or move generator by grasping the
louvers.  Doing  so  may  bend  or  damage  the  sheet
metal.
Suitable Mounting Surface
See  Figure 3-4.  Prepare  a  rectangular  area
approximately 5 in (127 mm) deep (A) and approximately
3 in (76.2 mm)  longer  and wider (B) than the generator
on all sides. 
Figure 3-4. Compacted Gravel or Concrete Pad
Select base type as desired or as required by local laws
or codes. The generator is typically placed on pea gravel,
crushed  stone,  or  a  concrete  pad.  Follow  all  applicable
codes if a concrete pad is required.
Verify  surface  where  generator  will  be  mounted  is
compacted,  leveled,  and  will  not  erode  over  time.
Generator must be level within 0.5 in (13 mm) all around. 
Placement on Roofs, Platforms, and 
Other Supporting Structures
Where  required  to  place  generator  on  a  roof,  platform,
deck,  or  other  supporting  structure,  generator  must  be
placed in accordance with the requirements in NFPA 37,
Section 4.1.3. Generator can be located 18 in (457 mm)
from  structures  having  combustible  walls  and  5  ft  (1.52
m)  from  any  operable  opening  in  the  structure.  Surface
beneath  the  generator  and  beyond  must  be
noncombustible  to  a  minimum  distance  of  12  in  (30.5
cm). Contact local Building Inspection Department or fire
department to determine which noncombustible materials
are approved for installation.
B
A
000856










