Product Manual
Table Of Contents
- Section 1: Safety Information
- Section 2: General Information
- Section 3: Operation
- Site Prep Verification
- Generator Enclosure
- Auxiliary Shutdown Switch
- Control Panel Interface
- Using the AUTO/OFF/MANUAL Interface
- Operating Modes
- Interface Menu Displays
- Menu System Navigation
- Setting the Exercise Timer
- Battery Charger
- Manual Transfer Operation
- Automatic Transfer Operation
- Automatic Sequence of Operation
- Shutting Generator Down While Under Load or During a Utility Outage
- Section 4: Maintenance
- Maintenance
- Preparing for Maintenance
- Performing Scheduled Maintenance
- Service Schedule
- Checking Engine Oil Level
- Changing the Oil and Oil Filter
- Servicing the Air Cleaner
- Spark Plug(s)
- Valve Clearance Adjustment
- Battery Maintenance
- Cleaning the Sediment Trap
- Post Maintenance Checks
- Attention After Submersion
- Corrosion Protection
- Remove From and Return To Service Procedure
- Section 5: Troubleshooting / Quick Reference Guide
Troubleshooting / Quick Reference Guide
36 Owner’s Manual for 60 Hz Air-Cooled Generators
No transfer to
standby after
utility source
failure
MLCB (generator disconnect) is OFF
(OPEN).
Reset MLCB (generator disconnect) to ON
(CLOSED).
Faulty transfer switch coil.
Contact an IASD for assistance.
Faulty transfer relay.
Transfer relay circuit open.
Faulty control logic board.
Engine may be warming up. See Cold Smart
Start.
Check controller screen to verify status.
Unit consumes
large amounts of
oil
Excessive engine oil. Adjust oil to correct level.
Faulty engine breather. Contact an IASD for assistance.
Incorrect type or viscosity of oil. See Engine Oil Requirements.
Damaged gasket, seal, or hose. Inspect for oil leaks.
Restricted air filter. Replace air filter.
Wi-Fi network
connection
broken or
intermittent
Various. See Wi-Fi module owner’s manual.
* Contact an IASD for assistance.
Problem Cause Correction