Electrical Connections
Installation Guidelines for 60 Hz Air-Cooled Generators 29
Section 6: Electrical Connections
Generator Connections
See Figure 6-1. The electrical wiring enclosure is located
behind  an  access  panel  on  intake  end  of  unit.  Remove
intake  side  panel  as  directed  in  Intake Side Panel
Removal, and then remove access panel. Connect wires
according to diagram and tables.
1. Remove main AC / control wiring  knock-out  plugs
from back of generator.
2. Using  appropriate  wiring  hole,  install  conduit  and
main AC and control wires between generator and
transfer switch.
3. Close  unused  hole  with  a  NEMA  3R  rated  plug
(field-supplied).
NOTE: All conductors are to be rated for minimum 300V.
Control system interconnections may consist of N1, N2,
and T1, and leads 23 and 194. All of the generator con-
trol wiring circuits are Class 1 remote control or signaling
circuits.  Class  1  circuits  are  required  to  be  installed  in
accordance  with  Part  1  of  NEC Article  300  and  with  a
NEC  recognized  Chapter  3  wiring  method.  The  use  of
low voltage cables for the generator control circuit wiring
is  prohibited.  See  instruction  manual  of  the  specific
engine  generator  for  wiring  connection  details.  Recom-
mended wire gauge sizes for this wiring depends on wire
length, as recommended in Table 6-3.
Exception:  Conductors  of  AC  and  DC  circuits,  rated
1000 volts nominal or less, shall be permitted to occupy
the  same  equipment,  cable,  or  conduit.  All  conductors
shall have an insulation rating equal to at least the maxi-
mum circuit  voltage  applied  to  any  conductor  within  the
equipment, cable, or conduit. See NEC 300.3(C)(1).
4. See Figure 6-1. Strip insulation from wire ends. Do
not  remove  excessive  insulation.  Route  sense
wires  through  supplied  wire  tie  (C1),  and  connect
to  sense  wire  terminal  block  (B).  Push  down  on
spring  loaded  connection  point  with  a  flat  head
screwdriver, insert wire, and release.
5. Using  the  same  process,  route  control  wires
through second supplied wire tie (C2), and connect
to control wire terminal block (A).
6. When  all  wires  are  securely  connected  to  correct
terminals, tighten wire ties and clip excess length.
NOTE: Only bare wire should be inserted into each ter-
minal. Do not insert any wire insulation into terminals.
NOTE:  Damage  caused  by  mis-wiring  of  the  intercon-
nect wires is not warrantable.