Install Manual
Table Of Contents
Site Selection and Preparation
16 Installation Guidelines for 60 Hz Air-Cooled Generators
Fire Codes, Standards, and Guidelines
Generator  installation  must  comply  strictly  with  ICC
IFGC,  NFPA  37,  NFPA  54,  NFPA  58,  and  NFPA  70
standards. These standards prescribe the minimum safe
clearances around and above the generator enclosure.
NFPA 37
NFPA  37  is  the  The  National  Fire  Protection
Association’s  standard  for  the  installation  and  use  of
stationary combustion engines. Its requirements limit the
spacing of an enclosed generator set from a structure or
wall,  and  require  generator  to  be  located  where  it  is
readily  accessible  for  maintenance,  repair,  and  first
responders.
NFPA 37, Section 4.1.4, Engines Located Outdoors:
Engines,  and  their  weatherproof  housings  if  provided,
installed outdoors shall be located at  least 5 ft (1.52 m)
from  openings  in  walls  and  at  least  5  ft  (1.52  m)  from
structures  having  combustible  walls.  A  minimum
separation  shall  not  be  required  where  the  following
conditions exist:
1. The adjacent wall of the structure has a fire resis-
tance rating of at least one hour.
2. The weatherproof enclosure is constructed of non-
combustible  materials  and  it  has  been  demon-
strated that a fire within the enclosure will not ignite
combustible materials outside the enclosure.
Annex A—Explanatory Material
A4.1.4  (2)  Means  of  demonstrating  compliance  are  by
means of full scale fire test or by calculation procedures.
Because  of  the  limited  spaces  frequently  available  for
installation,  it  has  become  apparent  that  exception  (2)
would be beneficial for many residential and commercial
installations.  The  manufacturer  contracted  with  an
independent testing laboratory to run full scale fire tests.
NOTE:  The  Southwest  Research  Institute  (SwRI)  is  a
nationally  recognized  third  party  testing  and  listing
agency. SwRI testing approves 18 in (457 mm) installa-
tion minimum from the rear panel of the generator to an
adjacent structure for fire protection. 
The criteria was to determine the worst case fire scenario
within  the  generator  and  to  determine  the  ignitability  of
items outside the engine enclosure at various distances.
The  enclosure  is  constructed  of  non-combustible
materials,  and  the  results  and  conclusions  from  the
independent testing lab indicated that any fire within the
generator  enclosure  would  not  pose  any  ignition  risk  to
nearby  combustibles  or  structures,  with  or  without  fire
service personnel response.
Figure 3-3. Southwest Research Institute Marking
http://www2.swri.org/www2/listprod/
DocumentSelection.asp?ProductID=973&IndustryID=2
Based on this testing and the requirements of NFPA 37,
Sec 4.1.4, the guidelines for installation of the generators
listed  above  are  changed  to  18  in  (457  mm)  from  the
back side of the generator to a stationary wall or building
For  adequate  maintenance  and  airflow  clearance,  the
area above the generator should be at least 5 ft (1.52 m)
with a minimum of 3 ft (0.91 m) at the front and ends of
the enclosure. This  includes  trees,  shrubs,  and bushes.
Vegetation  not  in  compliance  with  these  clearance
parameters  could  obstruct  air  flow.  In  addition,  exhaust
fumes from the generator could inhibit plant growth. See
Figure 3-2 and the accompanying descriptions.
Generator Maintenance 
Regular  maintenance  is  crucial  for  minimizing  exhaust
emissions  and  reducing  the  risk  of  fire  or  equipment
failure. For example:
• A dirty  air  filter  or  low  engine  oil  level  may  cause
engine to overheat. 
• Incorrect spark plug gaps may cause engine back-
firing and incomplete combustion.
IMPORTANT  NOTE:  See  Maintenance  section  of
generator  owner’s  manual  to  view  a  table  of
scheduled  maintenance  tasks  and  procedures.
Perform all maintenance tasks as directed.
002158










