Install Manual
Table Of Contents
Site Selection and Preparation
Installation Guidelines for 60 Hz Air-Cooled Generators 15
Fire Prevention
The generator must be installed at a safe distance away
from  combustible  materials.  Engine,  alternator,  and
exhaust  system  components  become  very  hot  during
operation.  Fire  risk  increases  if  unit  is  not  correctly
ventilated, is not correctly maintained, operates too close
to  combustible  materials,  or  if  fuel  leaks  exist.  Also,
accumulations of flammable debris within or outside the
generator enclosure may ignite.
Distance Requirements
See  Figure 3-2.  Minimum  clearances  must  be
maintained  around  the  generator  enclosure.  These
clearances  are  primarily  for  fire  prevention,  but  also  to
ensure sufficient room for removing front and end panels
for maintenance purposes.
Figure 3-2. Generator Distance Requirements
C
A
A
D
E
G
A
C
C
C
008782
F
B
ID Description Definition
A
Front and end 
clearance
Minimum clearance from the front and ends of generator must be 3 ft (0.91 m). This includes 
shrubs, bushes, and trees. 
B Rear clearance
Fuel and electrical connections are made here. 18 in (457 mm) minimum clearance per NFPA 
testing, labeling, and listing, unless state or local codes dictate otherwise. 
C
Windows, vents, 
and openings
No operable windows, doors, vents, window wells, or openings in the wall are permitted near any 
point of the generator. See Potential CO Entry Points for more information.
D Existing wall The generator should not be placed closer than 18 in (457 mm) from existing walls.
E Removable fence
A removable barrier (non-permanent; without footings) installed as a visual surround.
Removable fence panels for servicing cannot be placed less than 3 ft (0.91 m) in front of the 
generator.
F Overhead clearance
5 ft (1.52 m) minimum distance from any structure, overhang, or projections from wall. 
DO NOT install under wooden decks or structures.
G
Maintenance and 
servicing
Maneuvering space around generator for performing routine maintenance tasks such as battery 
replacement and engine service. Do not attempt to conceal generator with shrubs, bushes, or 
plants.