Spec Sheet
4 of 5
16/20/22 kW
16/20/22 kW switch options
®
Model G007036-0 (16 kW)
No. of Poles 2
Current Rating (Amps) 100
Voltage Rating (VAC) 120/240, 1Ø
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
65%
Return to Utility* approx. 15 sec.
Exercise bi-weekly for 12 minutes* Standard
UL Listed Standard
Total of Pre-wired Circuits
No. 15 A 120 V
No. 20 A 120 V
No. 20 A 240 V
No. 30 A 240 V
No. 40 A 240 V
No. 50 A 240 V
16
5
5
1
-
1
1
Tandem Breaker Capability 8 spaces
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
10,000
Limited Circuit Switch
• 16 circuits.
• Electrically operated, mechanically-held contacts for fast, positive connections.
• Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 30 millisecond transfer time.
• Dual coil design.
• Rated for both copper and aluminum conductors.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA 3R aluminum outdoor enclosure allows for indoor or outdoor mounting
flexibility.
• Multi listed for use with 1" standard, tandem, GFCI and AFCI breakers from
Siemens, Murray, Eaton and Square D for the most flexible and cost effective install.
Wire Ranges
Conductor Lug Neutral Lug Ground Lug
2/0 - #14 2/0 - #14 2/0 - #14
Dimensions
Dimensions
Service Rated Smart Switch Features
• Includes Digital Power Management Technology standard (DPM).
• Intelligently manages up to four air conditioner loads with no
additional hardware.
• Up to four more large (240 VAC) loads can be managed when used in
conjunction with Smart Management Modules (SMMs).
• Electrically operated, mechanically-held contacts for fast, clean
connections.
• Rated for all classes of load, 100% equipment rated, both inductive and
resistive.
• Up to four more large (120/240 VAC) loads can be managed when used in
conjunction with 50 amp Power Management Modules (PMM**).
• 2 pole, 250 VAC contactors.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
• NEMA 3R aluminum outdoor enclosure allows for indoor or outdoor
mounting flexibility.
• Main contacts are silver plated or silver alloy to resist welding and
sticking.
Model
G007037-0 (16 kW)/G007039-0 (20 kW)/
G007043-0 (22 kW)
No. of Poles 2
Current Rating (Amps) 200
Voltage Rating (VAC) 120/240, 1Ø
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
65%
Return to Utility* approx. 13 sec.
Exercise weekly for 12 minutes* Standard
UL Listed Standard
Enclosure Type NEMA/UL 3R
Withstand Rating (Amps) 22,000
Lug Range 250 MCM - #6
H2
DEPTH
H1
W2
W1
200 Amps 120/240, 1ø
Open Transition Service Rated
Height Width
Depth
H1 H2 W1 W2
in 27.24 30.0 11.4 13.5 7.09
mm 692.0 762.4 289.0 343.0 180.0
*Function of Evolution Controller
* Function of Evolution Controller
Exercise can be set to weekly or monthly
200 Amps 120/240, 1ø
Open Transition Service Rated
Height Width
Depth
H1 H2 W1 W2
in
27.24 30.0 11.4 13.5 7.09
mm 692.0 762.4 289.0 343.0 180.0
H2
DEPTH
H1
W2
W1