16/20/22 kW
16/20/22 kW switch options
®
Model G007036-0 (16 kW)
No. of Poles 2
Current Rating (Amps) 100
Voltage Rating (VAC) 120/240, 1Ø
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
65%
Return to Utility* approx. 15 sec.
Exercise bi-weekly for 12 minutes* Standard
UL Listed Standard
Total of Pre-wired Circuits
No. 15 A 120 V
No. 20 A 120 V
No. 20 A 240 V
No. 30 A 240 V
No. 40 A 240 V
No. 50 A 240 V
16
5
5
1
-
1
1
Tandem Breaker Capability 8 spaces
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
10,000
Limited Circuit Switch
• 16 circuits.
Electrically operated, mechanically-held contacts for fast, positive connections.
Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 30 millisecond transfer time.
• Dual coil design.
• Rated for both copper and aluminum conductors.
Main contacts are silver plated or silver alloy to resist welding and sticking.
NEMA 3R aluminum outdoor enclosure allows for indoor or outdoor mounting
flexibility.
Multi listed for use with 1" standard, tandem, GFCI and AFCI breakers from
Siemens, Murray, Eaton and Square D for the most flexible and cost effective install.
Wire Ranges
Conductor Lug Neutral Lug Ground Lug
2/0 - #14 2/0 - #14 2/0 - #14
Dimensions
Dimensions
Service Rated Smart Switch Features
• Includes Digital Power Management Technology standard (DPM).
• Intelligently manages up to four air conditioner loads with no
additional hardware.
• Up to four more large (240 VAC) loads can be managed when used in
conjunction with Smart Management Modules (SMMs).
Electrically operated, mechanically-held contacts for fast, clean
connections.
Rated for all classes of load, 100% equipment rated, both inductive and
resistive.
Up to four more large (120/240 VAC) loads can be managed when used in
conjunction with 50 amp Power Management Modules (PMM**).
• 2 pole, 250 VAC contactors.
• Service equipment rated, dual coil design.
• Rated for both aluminum and copper conductors.
NEMA 3R aluminum outdoor enclosure allows for indoor or outdoor
mounting flexibility.
Main contacts are silver plated or silver alloy to resist welding and
sticking.
Model
G007037-0 (16 kW)/G007039-0 (20 kW)/
G007043-0 (22 kW)
No. of Poles 2
Current Rating (Amps) 200
Voltage Rating (VAC) 120/240, 1Ø
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
65%
Return to Utility* approx. 13 sec.
Exercise weekly for 12 minutes* Standard
UL Listed Standard
Enclosure Type NEMA/UL 3R
Withstand Rating (Amps) 22,000
Lug Range 250 MCM - #6
H2
DEPTH
H1
W2
W1
200 Amps 120/240, 1ø
Open Transition Service Rated
Height Width
Depth
H1 H2 W1 W2
in 27.24 30.0 11.4 13.5 7.09
mm 692.0 762.4 289.0 343.0 180.0
*Function of Evolution Controller
* Function of Evolution Controller
Exercise can be set to weekly or monthly
200 Amps 120/240, 1ø
Open Transition Service Rated
Height Width
Depth
H1 H2 W1 W2
in
27.24 30.0 11.4 13.5 7.09
mm 692.0 762.4 289.0 343.0 180.0
H2
DEPTH
H1
W2
W1