Section 9  Quick Reference Guide
9.1 — System Diagnosis
Table 9-1. System Diagnosis
Problem LED Things to Check Active Alarm Solution
Unit running in AUTO but 
no power in house.
GREEN Check MLCB. NONE Check MLCB if the MLCB is in the ON 
position. If it is in the ON position contact 
the servicing dealer.
Unit shuts down during 
operation.
RED Check the LED’s / 
Screen for alarms.
HIGH 
TEMPERATURE
Check ventilation around the generator, 
intake, exhaust and rear of generator. If no 
obstruction contact serving dealer.
Unit shuts down during 
operation.
RED Check the LED’s / 
Screen for alarms.
OVERLOAD 
REMOVE LOAD
Clear alarm and remove household loads 
from the generator. Put back in AUTO and 
restart.
Unit was running and 
shuts down, attempts to 
restart.
RED check the LED’s / 
Screen for alarms.
RPM SENSE LOSS Clear alarm and remove household loads 
from the generator. Put back in AUTO and 
restart. It may be a fuel issue so contact 
the servicing dealer.
Unit will not start in 
AUTO with utility loss.
NONE See if screen says unit 
not activated.
NOT ACTIVATED Refer to activation section in owners man-
ual.
Unit will not start in 
AUTO with utility loss.
GREEN Check screen for start 
delay countdown.
None If the start up delay is greater than 
expected, contact servicing dealer to 
adjust from 2 to 1500 seconds.
Unit will not start in 
AUTO with utility loss.
RED Check the LED’s / 
Screen for alarms.
LOW OIL
 PRESSURE
Check Oil Level / Add Oil Per Owners 
Manual. If oil level is correct contact servic-
ing dealer.
Unit will not start in 
AUTO with utility loss.
RED Check the LED’s / 
Screen for alarms.
RPM SENSE LOSS Clear alarm. Check the battery using the 
control panel under the MAIN menu using 
the BATTERY MENU option. If it states 
battery is GOOD contact servicing dealer. 
If it states CHECK BATTERY replace the 
battery.
Unit will not start in 
AUTO with utility loss.
RED Check the LED’s / 
Screen for alarms.
OVERCRANK Check fuel line shutoff valve is in the ON 
position. Clear alarm. Attempt to start the 
unit in MANUAL. If it does not start or starts 
and runs rough, contact servicing dealer.
Unit will not start in 
AUTO with utility loss.
RED Check the LED’s / 
Screen for alarms.
LOW VOLTS 
REMOVE LOAD
Clear alarm and remove household loads 
from the generator. Put back in AUTO and 
restart.
Unit will not start in 
AUTO with utility loss.
RED Check the LED’s / 
Screen for alarms.
FUSE PROBLEM Check the 7.5amp fuse. If it is bad replace 
it with an ATO 7.5Amp fuse, if not contact 
servicing dealer.
Unit will not start in 
AUTO with utility loss.
RED Check the LED’s / 
Screen for alarms.
OVERSPEED Contact servicing dealer.
Unit will not start in 
AUTO with utility loss.
RED Check the LED’s / 
Screen for alarms.
UNDERVOLTAGE Contact servicing dealer.