Fuel Conversion/Gas Connections
Installation Guidelines for Air-Cooled Generators 25
Figure 5-6. Typical Natural Gas Vapor Installation
Figure 5-7. Typical LP Vapor Installation
BTU and Pressure Decal
0000001
GAS MAIN
2-5 PSI
TRAP
MANUAL SHUT
OFF VALVE
GAS METER CAPABLE OF
PROVIDING NATURAL GAS
AT THE REQUIRED VOLUME
BEST PRACTICE SPECIFIED BY THE REGULATOR
MANUFACTURER
NG BTU = CUBIC FEET/HOUR X 1000
11 kW and Below =
5"-7" WC REGULATOR
16 kW and Above =
3.5"-7" WC REGULATOR
FUEL PRESSURE
10-12” WC
TRAP
MANUAL SHUT
OFF VALVES
PRIMARY REGULATOR
(SUPPLIED BY INSTALLING
CONTRACTOR)
BEST PRACTICE SPECIFIED BY THE REGULATOR
MANUFACTURER
LP BTU = CUBIC FEET/HOUR X 2520