Install Manual
Table Of Contents
- Installation Guidelines
- FREQUENTLY ASKED QUESTIONS
- Table of Contents
- Section 1 Safety and General Information
- Section 2 Unpacking and Inspection
- Section 3 Site Selection and Preparation
- Section 4 Generator Placement
- Section 5 Fuel Conversion/Gas Connections
- Section 6 Electrical Connections
- Section 7 Control Panel
- Section 8 Troubleshooting
- Section 9 Quick Reference Guide
- Section 10 Accessories
- Section 11 Diagrams
- Part No. 0K5804
ii Installation Guidelines for Air-Cooled Generators
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.
FREQUENTLY ASKED QUESTIONS
ThislistofFrequentlyAskedQuestions(FAQs)arethefrequentlyaskedinstallationquestions
thatpertaintoALLHomeStandbymodels.
Somequestionsmaynotbeapplicabletothemodel(s)coveredinthispublication.
PleasereviewtheSafetySectionofyourproduct’sOwnersorInstallationManualbeforeoperatingyourHome
StandbyGenerator.
Q:
DoIhavetosupplythegeneratorwiththe100%loadedBTUratedfuelsupplyandpipesize?
A:
Yes, the generator needs the 100% loaded BTU fuel rating to start, run and handle loads. The fuel pipe must
be sized for 100% load, regardless of the load.
Q:
Can I use a fuel shut off valve that is not “Full Flow Rated”?
A:
No, it must be a Full Flow Rated valve and must also match the required fuel pipe ID dimensions.
Q:
Do pipe elbows, tees, drip legs, etc. affect pipe size and flow?
A:
Yes, they are restrictions to gas flow. You must add 2.5 ft. (.76 m) per each elbow, tee, etc. to the overall cal-
culated distance from the source to the generator.
Q:
Can I leave the unit on the shipping pallet and install it?
A:
No, it must be installed per local jurisdiction, code and the instructions as outlined by the manufacturer.
Q:
Can the generator be mounted indoors or in a structure?
A:
No, it is designed, manufactured and sold for outdoor use only!
Q:
Can I run the Main AC and Control Wires in the same conduit?
A:
Yes, this wiring can be run in the same conduit if the appropriate rated wire and insulation is used and it
meets code.
Q:
Can the Transfer Switch be mounted outdoors?
A:
Only if it’s a NEMA 3R rated transfer switch.