Install Drawing
18
To properly use this chart, fi nd the kW rating of the generator in the left column, and trace to the right. The number to the right is the maximum length
(measured in feet / meters) allowed for the pipe sizes on top. The pipe sizes are measured by inside diameter (ID) to include any fi ttings, valves
(must be full fl ow), elbows, tees or angles. Add 2.5ft. (.76m) per any bend, tee or angle in the pipe to the overall distance.
For pressures below 5" of water column (9mm mercury) down to 3.5” of water
column (7mm mercury)
To properly use this chart, fi nd the kW rating of the generator in the left column, and trace to the right. The number to the right is the maximum length
(measured in feet / meters) allowed for the pipe sizes on top. The pipe sizes are measured by inside diameter (ID) to include any fi ttings, valves
(must be full fl ow), elbows, tees or angles. Add 2.5ft. (.76m) per any bend, tee or angle in the pipe to the overall distance.
238)4MTIWM^IWEVIYWMRKEWIGSRHWXEKIVIKYPEXSV
238)8LIQMRMQYQ04XEROWM^IMWKEPPSRW0YRPIWWYRMXGEPGYPEXMSRWHMGXEXIYWISJEPEVKIVXERO:IVXMGEPXEROW[LMGL
EVIQIEWYVIHMRTSYRHWSVOMPSKVEQW[MPPRSXYWYEPP]QIIXXLIQMRMQYQXEROWM^IVIUYMVIQIRX%PFOKZIVXMGEPXEROWM^I
QMRMQYQMWVIUYMVIH
+%74-4)7->-2+-732)3*8,)1378'311320=1%()1-78%/)7%4634)60=7->)(+%74-4)-7'6-8-
'%0838,)4634)634)6%8-323*8,)+)2)6%8368,)+)2)6%836-20)87->),%723&)%6-2+32
8,)4634)6+%74-4)7->)
238)8,)+%779440=%2(4-4)1978&)7->)(%803%(&891)+%.390)6%8-2+
1. Both natural gas and LP Vapor are highly volatile substances, so strict adherence to all safety procedures, codes, standards and
regulations is essential.
Gas line connections should be made by a certified plumber familiar with local codes. Always use AGA-approved gas pipe and a quality
pipe sealant or joint compound.
Verify the capacity of the natural gas meter or the LP tank in regards to providing sufficient fuel for both the generator and other operating
appliances.
• Fuel Regulator installed per laws or regulator manufacturer’s specifi cations
• AGA approved gas pipe
• Flexible fuel line
– Do not bend!!!
– Do not attach directly to generator
– Check all connections for leaks
• Sediment trap near generator (if applicable or required by code)
• Full fl ow rated shut-off near generator per local jurisdiction or code