Install Drawing

17
238)6IUYMVIHJYIPTVIWWYVIJSVREXYVEPKEWMWx[EXIVGSPYQRQQQIVGYV]8LIVIUYMVIHJYIPTVIWWYVIJSV04:ETSVMWx
[EXIVGSPYQRQQQIVGYV]
These are approximate values, use the appropriate spec sheet or owner’s manual for speci c values.
Unit
Nat. Gas LP Vapor
1/2 Load Full Load 1/2 Load Full Load
7 / 8 kW 78 / 2.21 121 / 3.43 0.87 / 3.29 1.42 / 5.37
10 / 11 kW 124 / 3.51 195 / 5.52 1.18 / 4.45 1.92 / 7.28
13 / 13 kW 157 / 4.45 255 / 7.22 1.64 / 6.2 2.95 / 11.15
14 / 14 kW 177 / 5.01 279 / 7.9 1.85 / 6.99 3.07 / 11.61
15 / 15 kW 185 / 5.24 296 / 8.38 1.83 / 6.91 2.86 / 10.82
16 / 16 kW 193 / 5.47 312 / 8.83 1.9 / 7.2 3.19 / 12.07
16 / 17 kW 193 / 5.47 312 / 8.83 1.99 / 7.53 3.57 / 13.53
18 / 20 kW 205 / 5.8 308 / 8.72 2.08 / 7.87 3.85 / 14.57
* Natural gas is in cubic feet per hour / cubic meters per hour.
** LP is in gallons per hour / liters per hour.
*** Values given are approximate.
:IVMJ]XLEXKEWQIXIVMWGETEFPISJTVSZMHMRKIRSYKLJYIP S[XSMRGPYHILSYWILSPHETTPMERGIWERHEPPSXLIVPSEHW
+EWISYWJYIPWWYGLEWREXYVEPKEWERHPMUYMHTVSTERI04KEWEVILMKLP]I\TPSWMZI)ZIRXLIWPMKLXIWXWTEVOGERMKRMXIWYGLJYIPW
ERHGEYWIERI\TPSWMSR2SPIEOEKISJJYIPMWTIVQMXXIH2EXYVEPKEW[LMGLMWPMKLXIVXLEREMVXIRHWXSGSPPIGXMRLMKLEVIEW04KEW
MWLIEZMIVXLEREMVERHXIRHWXSWIXXPIMRPS[EVIEW
238)%QMRMQYQSJSRIETTVSZIHJYPPJPS[QERYEPWLYXSJJZEPZIQYWXFIMRWXEPPIHMRXLIKEWISYWJYIPWYTTP]PMRI8LIZEPZIQYWXFI
IEWMP]EGGIWWMFPI0SGEPGSHIWHIXIVQMRIXLITVSTIVPSGEXMSR
238)8,)+%779440=%2(4-4)1978&)7->)(%803%(&891)+%.390)6%8-2+
First, determine what size pipe is required. Refer to NFPA 54 for NG or NFPA 58 for LP for further information.
Always refer to the owner’s manual for the proper BTU / megajoule and required gas pressures. To calculate BTU or Megajoules:
Natural Gas: BTU=Cubic feet / hour x 1000
Megajoules=Cubic meters / hour x 37.26
Liquid Propane Vapor: BTU=Cubic feet / hour x 2500
Megajoules=Cubic meters / hour x 93.15
Start by measuring the distance from the generator to the gas source. The generator should be plumbed directly from the source, not off the end
of an existing system.
When measuring the pipe length, add 2.5ft. (.76m) for every angle or bend in the pipe and add that to the overall pipe distance.