Spec Sheet
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with
BS5514, ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum
power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F).
SPECIFICATIONS
GENERATOR Model 05504 (17 kW) Model 05505 (17 kW)
Rated Maximum Continuous Power Capacity (LP) 17,000 Watts* 17,000 Watts*
Rated Maximum Continuous Power Capacity (NG) 16,000 Watts* 16,000 Watts*
Rated Voltage 120/240 120/240
Rated Maximum Continuous Load Current
240 Volts 70.8 LP/66.6 NG 70.8 LP/66.6 NG
Total Harmonic Distortion Less than 5% Less than 5%
Main Line Circuit Breaker 65 Amp 65 Amp
Phase 1 1
Number of Rotor Poles 2 2
Rated AC Frequency 60Hz 60Hz
Power Factor 1 1
Battery Requirement (not included) Group 26R
12 Volts and
525 Cold-cranking
Amperes Minimum
Group 26R
12 Volts and
525 Cold-cranking
Amperes Minimum
Unit Weight (lbs./kilos) 455 Pounds 414 Pounds
Dimensions (L” x W” x H”) 48 x 25 x 29 48 x 25 x 29
Sound output in dB(A) at 23 ft. with generator operating at normal load 66 66
Sound output in dB(A) at 23 ft. with generator in Whisper-Test™ low speed exercise mode 60 60
ENGINE Model 05504 (17 kW) Model 05505 (17 kW)
Type of Engine GENERAC OHVI V-TWIN GENERAC OHVI V-TWIN
Number of Cylinders 2 2
Rated Horsepower 32 @ 3,600 rpm 32 @ 3,600 rpm
Displacement 992cc 992cc
Cylinder Block Aluminum w/Cast
Iron Sleeve
Aluminum w/Cast
Iron Sleeve
Valve Arrangement Overhead Valve Overhead Valve
Ignition System Solid-state w/Magneto Solid-state w/Magneto
Governor System Electronic Electronic
Compression Ratio 9.5:1 9.5:1
Starter 12 Vdc 12 Vdc
Oil Capacity Including Filter Approx. 1.9 Qts. Approx. 1.9 Qts.
Operating RPM 3,600 3,600
Fuel Consumption
Natural Gas cu.ft./hr.
1/2 Load
Full Load
Liquid Propane ft
3
/hr (gal/hr)
1/2 Load
Full Load
183
261
59 (1.61)
94 (2.57)
183
261
59 (1.61)
94 (2.57)
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 11 to 14 inches of water column for LP gas
CONTROLS
2-Line Plain Text LCD Display Simple user interface for ease of operation
Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser
-Off Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (start) Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)
Engine Warm-up 10 seconds
Engine Cool-Down 1 minute
Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
2.5 Amp Timed Trickle Battery Charger Standard
Automatic Voltage Regulator w/Overvoltage Protection Standard
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard, 72Hz
High Temperature Shutdown Standard
Overcrank Protection Standard
Safety Fuse Standard
®