Spec Sheet
©2009 Gen-Tran Corporation. Specifications subject to change without notice. Protected by US Patents US 6,861,596 B2, D562,266 S and others pending. Ovation and PowerPause are trademarks of Gen-Tran Corporation.
PN 50486 Rev B
Ovation
™
Series Automatic Transfer Switches
PRODUCT SPECIFICATIONS
DESCRIPTION
: A series of service entrance rated, open-transition automatic transfer switches integrated with a load center, offered in NEMA Type 1 or 3R enclosures,
for use in residential and light commercial single phase standby power applications and compatible with stationary generators up to 50 kW. PowerPause™ Load
Management Modules and surge suppression options are factory or field installable.
MODEL
POLES CURRENT
(Utility/Gen)
VOLTAGE
(nominal, AC)
PHASE FREQUENCY
(nominal, Hz)
ENCLOSURE
RATING (NEMA)
ENCLOSURE SIZE
(HxWxD inches)
BRANCH
CIRCUITS
MOUNT
Flush/Surface
WEIGHT
(lbs)
LUG
CAPACITY
ATS1001D 2 100/100 120/240 1 60 Type 1 24 x 14.31 x 3.93 14 F/S 28 2/0 Al/Cu
ATS1001R 2 100/100 120/240 1 60 Type 3R 28 x 14.5 x 4.25 16 S 27 2/0 Al/Cu
ATS2001D 2 200/125 120/240 1 60 Type 1 42 x 14.31 x 3.93 38 F/S 46 300 Kcmil Al/Cu
ATS2001R 2 200/125 120/240 1 60 Type 3R 41 x 4.5 x 4.25 38 S 43 300 Kcmil Al/Cu
ATS2002R 2 200/200 120/240 1 60 Type 3R 23.5 x 18.5 x 4.25 4 S 23 300 Kcmil Al/Cu
CONTROLLER
Voltage (nominal): 240 VAC (+/- 3%)
Pickup <204 or >270 VAC
Dropout <190 or >280 VAC
Frequency (nominal): 60 Hz (+/- 2%)
Pickup <57 or >63 Hz
Dropout <54 or >66 Hz
Time delays:
Gen Start 5 seconds (utility voltage or frequency out of range)
Load to Gen 10 seconds (verify voltage and frequency)
Retransfer to Util 60 seconds (verify voltage and frequency)
Gen Cooldown 300 seconds
Generator Exerciser:
Repeat interval 0, 7, 14, or 28 days
Duration 15 minutes (10 min transferred, 5 min cool down)
Load transfer Optional
Diagnostic Monitoring:
Gen start/stop failure (fast flash LED 4 – GENERATOR POWER)
Gen over/under voltage/frequency (slow flash LED 4 – GENERATOR POWER)
Utility over/under voltage/frequency (slow flash LED 2 – UTILITY POWER)
Transfer failure to generator (slow flash LED 5 – GENERATOR LOAD)
Transfer failure to utility (slow flash LED 1 – UTILITY LOAD)
Motor drive fault (fast flash LED 3 – LOAD)
Battery failure (fast flash LEDs 2+5 – UTILITY POWER + GENERATOR LOAD)
Generator Signaling:
Supports 2 or 4 wire (ON, +12V) or (CRANK, ON, +12V, -12V)
PowerPause™ Load Management modules (optional, sold separately)
Dynamic load management for up to six (6) 2 pole standby circuits
PowerPause™ Relay Box (optional, sold separately)
ENVIRONMENTAL CONDITIONS
Temperature: Operating: -4°F to +122°F (-20°C to +50°C)
Storage: -67°F to +149°F (-55°C to + 65°C)
Humidity: 95% Relative humidity
WITHSTAND/CLOSING RATING
10K AIC standard, 22K AIC optional (22K AIC standard on ATS2001D/R)
COMPATIBLE BRANCH CIRCUIT BREAKERS
Siemens® QAF, QFH, QE, QEH, QFP, QNR, QNRH,
QP, QF, QPF, QPH, QT, QSAP, HQP
Cutler-Hammer: BD, BR, BQ, GFC
Square D HOM
GE THQL, THHQL
AGENCY APPROVALS
• cULus67
• Conforms to requirements of NEC/NFPA 70, Article 702.5 and 702.6 for
Optional Standby Systems.
WARRANTY
Covers defects in materials and workmanship for 24 months from date of purchase,
subject to inspection. Must be installed by a qualified electrician in accordance with the
National Electrical Code and all applicable local codes, with all necessary permits and
inspections prior to operation.
For more information, call 1-888-GEN-TRAN or visit www.gen-tran.com
.