User's Manual Part 1

MC75 Hardware Interface Description
Strictly confidential / Draft
s
MC75_V00.190a Page 32 of 91 15.02.2005
3.2.3.4 Undervoltage Shutdown if no Battery NTC is Present
The undervoltage protection is also effective in applications, where no NTC connects to the
BATT_TEMP terminal. Thus, you can take advantage of this feature even though the
application handles the charging process or MC75 is fed by a fixed supply voltage. All you
need to do is executing the write command AT^SBC=<current> which automatically enables
the presentation of URCs. You do not need to specify <current>.
Whenever the supply voltage falls below the specified value (see table TBD.) the URC
^SBC: Undervoltage
appears several times before the module switches off.
3.2.3.5 Overvoltage Shutdown
In the event of the voltage rising above the maximum voltage (see Table TBD) the module
sends a URC and then performs an orderly shutdown. Further details: TBD
Keep in mind that several MC75 components are directly linked to BATT+ and, therefore, the
supply voltage remains applied at major parts of MC75, even if the module is switched off.
Especially the power amplifier is very sensitive to high voltage and might even be destroyed.