Dimensions and cut-out
Installation with panel mounting
As well as the actual instrument and these instructions
for use, the controller package also contains:
•panelfixingkit(A)
•1protectivesealagainstdustandwaterspray(B)
Fit the instrument to the panel as shown in the figure.
Warnings and instructions for mounting to the panel
Instructions for installation category II,
pollution level 2, double isolation.
The equipment is intended for permanent indoor
installations within their own enclosure or panel
mounted enclosing the rear housing and exposed
terminals on the back
•onlyformodelswith11...27Vac/dcpowersupply:
supply from Class 2 or low voltage limited energy
source
•thepowersupplylinesmustbeseparatefromthe
controller input and output ones
•grouptheinstrumentstogetherkeepingthemseparate
from the powered part of the relay
•donotinstallhigh-powerremoteswitches,contactors,
relays, thyristor power units (especially the “phase
angle” type), motors, etc. in the same switchboard
•avoiddust,humidity,corrosivegassesandheat
sources
•donotblocktheventilationholes:theworking
temperature must be between 0...50°C
•surroundingair:50°C
•use60/75°Ccopper(Cu)conductoronly,wiresize
range 2x N. 22 - 14AWG, Solid/Stranded
•useterminaltighteningtorque0.5Nm
Nominal ambient conditions
Before supplying the Indicator with power,
make sure that the mains voltage is the same
as that shown in the last number of the order
code.
Example:
450 – x – R – 0 = 11...27Vac/dc
450 – x – R – 1 = 100...240Vac
Altitude Up to 2000m
Working/storage 0..50°C/-20...70°C
temperature
Non condensing 20...85%
relative humidity
99
10
45
45
48
70
70
63
48
A
B
AB
Panel