Operation Manual
English
Operation Manual
The door control DC MiniMax 3 S is designed for hold to run control of power operated
doors. The basic version is designed for hold to run operation only,
but it can be extended individually by an optional module.
Safety Directions
• In case of using DC MiniMax 3 S with a permanent mains connection, an all-pole main switch
with an appropriate back-up fuse must be provided.
• With three phase motor connection an external fuse in the main supply should be
max. 10A delayed.
• Before operation, check whether the permissible mains voltage range of the device corresponds
to the local mains voltage.
• With three phase motor connection it must have right phase rotation.
During installation, initial operation, maintenance and testing of the DC MiniMax 3 S it is
necessary to observe the safety and accident prevention regulations valid for the specific
application. Only trained electrical craftsmen should work on electrical equipment.
Technical Data
Model DC MiniMax 3 S
Supply voltage 230 VAC or 400 VAC
Frequency 50 Hz
Protection class
IP 54
A max. 10 A
Operation temperature - 10 C° to + 55 C°
Page 2 of 8 Revision 03