Owner manual

D
GB
F
E
I
Ru
27
09971-01.2015-DGbFEIRu
8| Technical data
Type
No. of cylinders
Displace-
ment
50/60Hz
(1450 / 1740
rpm)
Electrical data
Weight
Connections Oil
charge
Sound
pressure
level
Voltage Max.
Operating
current
PW 1 + 2
Max.
power
con
-
sumption
Starting
current
(rotorlocked)
PW 1 / PW 1 + 2
Dis-
charge
line
DV
Suction
line
SV
m
3
/h A kW A kg mm (inch) mm (inch) Ltr. dB(A)
HG6/1080-4
4
93,7 / 112,4 47 26,3 149 / 189 218
35 (1
3
/
8
) 54 (2
1
/
8
) 3,6
73 / 71 / 70
HG6/1080-4 S 93,7 / 112,4 57 31,0 172 / 212 223
HG6/1240-4
107,6 / 129,1
57 30,5 172 / 212 222
74 / 72 / 71
HG6/1240-4 S
107,6 / 129,1
71 36,0 204 / 250 224
HG6/1410-4
122,4 / 146,9
57 35,6 172 / 212 219
75 / 72 / 71
HG6/1410-4 S
122,4 / 146,9
71 42,6 204 / 250 222
1
2
3
2
4
380-420VY/YY-3-50HzPW
440-480VY/YY-3-60HzPW
PW = Part Winding
Winding ratio : 66% / 33%
L / M / H
5
Tolerance (± 10%) relative to the mean value of the voltage range.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
 For60Hzoperation,thespecicationshavetobemultipliedbythefactor
1.2. The max. working current remains unchanged.
- Take account of the max. operating current / max. power consumption for
design of fuses, supply lines and safety devices. Fuse: Consumption
category AC3
1
2
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections
L = low temperature (-35 / 40 °C), M = normal cooling (-10 / 45 °C),
H = air conditioning (5 / 50°C)
sound pressure level measured in
lowreectionmeasuringarea,measuringdistance1m.
Compressor operation at 50 Hz (1450 rpm), refrigerant R404A.
Valuesstatedareaveragevalues,tolerance±2dB(A).
5
3
4