3 | Areas of application
Thecompressorsarelledatthefactorywiththefollowingoiltype:
- for R134a, R404A/R507, R407C, R407F FUCHS Reniso Triton SE 55
- for R22 FUCHS Reniso SP 46
Compressorswithesteroilcharge(FUCHSRenisoTritonSE55)aremarkedwithanXinthetype
designation (e.g. HGX44e/665-4).
3.1 Refrigerants
HFKW / HFC: R134a, R404A/R507, R407C, R407F
• (H)FCKW/(H)CFC: R22
3.2 Oil charge
INFO
For refilling, we recommend the above oil types.
Alternatives: see lubricants table, Chapter 7.5
ATTENTION Compressor operation is possible within the operating limits
showninthediagrams.Pleasenotethesignicance
of the shaded areas. Thresholds should not be selected as
design or continuous operation points.
- Permissible ambient temperature (-20°C) - (+60°C)
- Max. permissible discharge end temperature 140°C.
-Max.permissibleswitchingfrequency12x/h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with supplementary cooling:
- Use only oils with high thermal stability.
- Avoid continuous operation near the threshold.
For operation with capacity regulator:
- The suction gas superheat temperature may need to be reduced
or set individually when operating near to the threshold.
Foroperationwithfrequencyconverter:
- The maximum current and power consumption must not be
exceeded.Inthecaseofoperationabovethemainsfrequency,the
application limit can therefore be limited.
When operating in the vacuum range, there is a danger of air
entering on the suction side. This can cause chemical reactions,
a pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!
3.3 Limits of application
ATTENTION The oil level must be in the
visible part of the sight glass;
damage to the compressor is
possible if overfilled or under-
filled!
Fig. 4
max.
min.
1,7 Ltr.
oil level
~
~