8 | Technical data
Type
No. of cylinders
Displacement
50 / 60 Hz
(1450 / 1740
rpm)
Electrical data Weight Connections
Oil charge
Voltage Max.
Operating
current
PW 1 + 2
Max.
power con-
sumption
Starting
current
(rotor locked)
PW 1 / PW 1 + 2
Discharge
line
DV
Suction
line
SV
m
3
/h A kW A kg mm (inch) mm (inch) Ltr.
HG44e/475-4
4
41,3 / 49,6 19 11,0 83 / 109 164
28 / 1
1
/
8
35 / 1
3
/
8
2,3
HG44e/475-4 S 41,3 / 49,6 23 13,1 115 / 150 168
HG44e/565-4
49,2 / 59,0 22 13,2 83 / 109 164
HG44e/565-4 S
49,2 / 59,0 26 15,6 133 / 171 170
42 / 1
5
/
8
HG44e/665-4
57,7 / 69,2 26 15,4 115 / 150 171
HG44e/665-4 S
57,7 / 69,2 30 18,3 133 / 171 168
HG44e/770-4
67,0 / 80,4 30 17,8 133 / 171 168
HG44e/770-4 S
67,0 / 80,4 35 21,4 133 / 171 168
1
2
3
2
4
380-420 V Y/YY - 3 - 50 Hz PW
440-480 V Y/YY - 3 - 60 Hz PW
PW = Part Winding
Winding ratio : 70% / 30%
Tolerance(±10%)relativetothemeanvalueofthevoltagerange.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
 For60Hzoperation,thespecicationshavetobemultipliedbythefactor1.2.
The max. working current remains unchanged.
- Take account of the max. operating current / max. power consumption for
design of fuses, supply lines and safety devices.
Fuse: Consumption category AC3
1
2
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections
3
4