User guide
22
D
GB
F
E
96280-12.2014-DGbFEIRu
NL B1 B2 12 14 11
PTC
Motor Protection INT69 G
Terminal box
Fig. 23
supply
Lock out
PTC1 PTC2
5| Electrical connection
5.6 Electronic trigger unit INT69 G
5.7 Connection of the trigger unit INT69 G
The compressor motor is tted with cold conductor temperature sensors (PTC) connected to the
electronic trigger unit INT69 G in the terminal box. In case of excess temperature in the motor
winding, the INT 69 G deactivates the motor contactor. Once cooled, it can be restarted only if the
electroniclockoftheoutputrelay(terminalsB1+B2)isreleasedbyinterruptingthesupplyvoltage.
The hot gas side of the compressor can also be protected against overtemperature using thermal
protectionthermostats(accessory).
The unit trips when an overload or inadmissible operating conditions occur. Find and remedy
the cause.
INFO Therelay switching outputis executedas a oatingchangeover
contact.Thiselectricalcircuitoperatesaccordingtothequiescent
current principle, i.e. the relay drops into a the idle position and
deactivates the motor contactor even in case of a sensor break or
open circuit.
INFO Connect the trigger unit INT69 G in accordance with the circuit dia-
gram. Protect the trigger unit with a delayed-action fuse (F) of max.
4 A. In order to guarantee the protection function, install the trigger
unitastherstelementinthecontrolpowercircuit.
ATTENTION
PTC cable on the trigger unit
INT69 G and terminals PTC 1 and
PTC 2 on the compressor termi-
nal board must not come into
contact with mains voltage.
This would destroy the trigger
unit INT69 G and PTC sensors.