Manual

D
GB
F
E
I
Ru
27
09958-12.2014-DGbFEIRu
8| Technical data
Type
No. of cylinders
Displace-
ment
50/60Hz
(1450 / 1740
rpm)
Electrical data
Weight
Connections
Oil charge
Sound
pressure
level
Voltage Max.
Operating
current
PW 1 + 2
Max.
power
consump
-
tion
Starting
current
(rotorlocked)
PW 1 / PW 1 + 2
Dis-
charge
line
DV
Suction
line
SV
m
3
/h A kW A kg mm (inch) mm (inch) Ltr. dB(A)
HG4/310-4
4
27,1 / 32,5 16 8,5 50 / 65 147
22 (
7
/
8
) 28 (1
5
/
8
)
2,7
59 / 60 / 60
HG4/310-4 S 27,1 / 32,5 18 9,0 57 / 75 149
HG4/385-4 33,5 / 40,2 18 9,5 57 / 75 149
61 / 61 / 60
HG4/385-4 S
33,5 / 40,2 27 12,5 82 / 107 152
HG4/465-4 40,5 / 48,6 18 11,0 57 / 75 148
28 (1
1
/
8
)
35 (1
3
/
8
)
64 / 63 / 62
HG4/465-4 S
40,5 / 48,6 27 13,0 82 / 107 151
HG4/555-4 48,2 / 57,8 27 12,9 82 / 107 150
66 / 64 / 62
HG4/555-4 S
48,2 / 57,8 34 15,2 107 / 140 153
HG4/650-4 56,6 / 67,9 27 15,7 82 / 107 152
42 (1
5
/
8
) 69 / 66 / 63
HG4/650-4 S
56,6 / 67,9 34 18,4 107 / 140 155
1
2
3
2
4
380-420VY/YY-3-50HzPW
440-480VY/YY-3-60HzPW
PW = Part Winding
Winding ratio : 66% / 33%
L / M / H
5
Tolerance (± 10%) relative to the mean value of the voltage range.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
 For60Hzoperation,thespecicationshavetobemultipliedbythefactor
1.2. The max. working current remains unchanged.
- Take account of the max. operating current / max. power consumption for
design of fuses, supply lines and safety devices. Fuse: Consumption
category AC3
1
2
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections
L = low temperature (-35 / 40 °C), M = normal cooling (-10 / 45 °C),
H = air conditioning (5 / 50°C)
sound pressure level measured in
lowreectionmeasuringarea,measuringdistance1m.
Compressor operation at 50 Hz (1450 rpm), refrigerant R404A.
Valuesstatedareaveragevalues,tolerance±2dB(A).
5
3
4