4| Compressor assembly
Setuponanevensurfaceorframewithsufcientload-
bearing capacity.
Single compressor preferably on vibration damper.
Duplex and parallel circuits always rigid.
Provideadequateclearanceformaintenancework.
Ensureadequatecompressorventilation.
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment.
Fig. 10
Fig. 11
Fig. 12
ATTENTION! Superheating can damage the valve.
Remove the pipe supports from the valve for soldering.
Only solder using inert gas to inhibit oxidation products (scale).
4.3 Pipe connections
INFO! Newcompressorsarefactory-lledwithinertgas(3barnitrogen).
Leave this service charge in the compressor for as long as possible
and prevent the ingress of air.
Check the compressor for transport damage before starting any
work.
4.2 Setting up
?
4.1 Storage and transport
Use transport eyelet.
Do not lift manually!
Use lifting gear!
Storage at (-30°C) - (+70°C), maximum permissible relative humidity
10% - 95%, no condensation
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Fig. 9
Fig. 8
ATTENTION! Attachments(e.g.pipeholders,additionalunits,fasteningparts,
etc.) directly to the compressor are not permissible!