User guide

D
GB
F
E
I
Ru
25
96178-11.2014-DGbFEIRu
8| Technical data
Type No. of
cylin-
ders
Displace-
ment
50/60Hz
(1450 / 1740
rpm)
Electrical data
Weight
Connections Oil
charge
Sound pres-
sure level
Voltage Max.
Operating
current
/ Y
Max.
power
consump
-
tion
Starting
current
(rotor
locked)
/ Y
Dis-
charge
line
DV
Suction
line
SV
m
3
/h A kW A kg mm(inch) mm(inch) Ltr. dB(A)
HGX34e/215-4 S
R407C
4
18,8 / 22,6 20,1 / 11,6 6,8 132 / 76 97
22 (
7
/
8
) 28 (1
1
/
8
) 1, 3
62 / 59 / 58
HGX34e/255-4 S
R407C
22,1 / 26,6 23,7 / 13,7 8,2 132 / 76 96 64 / 62 / 60,5
HGX34e/315-4 S
R407C
27,3 / 32,8 28,1 / 16,2 9,9 132 / 76 97 66 / 64 / 63
HGX34e/380-4 S
R407C
33,1 / 39,7 33,8 / 19,5 12,1 132 / 76 96 67 / 64,5 / 64
1
2
3
2
4
220-240 V / 380-420 V Y - 3 - 50 Hz
265-290 V / 440-480 V Y - 3 - 60 Hz
L / M / H
5
Tolerance(±10%)relativetothemeanvalueofthevoltagerange.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
 For60Hzoperation,thespecicationshavetobemultipliedbythefactor
1.2. The max. working current remains unchanged.
- Take account of the max. operating current / max. power consumption for
design of fuses, supply lines and safety devices. Fuse: Consumption
category AC3
1
2
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections
L=lowtemperature(-35/40°C),M=normalcooling(-10/45°C),
H=airconditioning(5/50°C)
sound pressure level measured in
lowreectionmeasuringarea,measuringdistance1m.
Compressoroperationat50Hz(1450rpm),refrigerantR404A.
Valuesstatedareaveragevalues,tolerance±2dB(A).
5
3
4