5| Electrical connection
ThecompressorandthetriggerunitMP10areoperationalwhentheH3LED(green)lights.
5.7 Function test of the trigger unit MP 10
Pos
Procedure
LED H1 LED H2 LED H3
red red green
1
Interrupt power supply (L1 or S1) OFF OFF OFF
Releasethemotortemperaturesensorconnection(1or2)
Releasethehotgastemperaturesensor(ifinstalled)(3or4)
2
Restore the power supply (L1 or S1) ON
Function check of motor temperature sensor: operational ON
Function check of hot gas temperature sensor: operational ON
3
Interrupt power supply again (L1 or S1) OFF OFF OFF
Reconnect terminals 1 or 2 and/or 3 or 4
4
Restore the power supply (L1 or S1): OFF OFF ON
MP 10 is operational again
Before start-up, troubleshooting or making changes to the control power circuit, check the functionality
of the trigger unit: