3 | Areas of application
Thecompressorsarelledwiththefollowingoiltypeatthefactory:
- for R134a, R404A, R507, R407C FUCHS Reniso Triton SE 55
- for R22 FUCHS Reniso SP 46
Compressorswithester oilcharge(FUCHS RenisoTritonSE55) aremarkedwithanXinthe type
designation (e.g. HGX34e/380-4A).
3.1 Refrigerants
HFKW / HFC: R134a, R404A, R507, R407C
• (H)FCKW/(H)CFC: R22
3.2 Oil charge
ATTENTION! Compressor operation is possible within the operating
limitsshowninthediagrams.Pleasenotethesignicance
of the shaded areas. Thresholds should not be selected as design
or continuous operating points.
- Permissible ambient temperature (-20°C) - (+60°C)
- Max. permissible discharge end temperature: 140°C
-Max.permissibleswitchingfrequency:8x/h
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with supplementary cooling:
- Use only oils with high thermal stability.
- Avoid continuous operation near the threshold.
Foroperationwithfrequencyconverter:
- The potential control range of the compressor is 25-70 Hz.
- Max. permissible current consumption must not be exceeded.
Atmax.rotationspeedtherefore,theapplicationlimitcanbereduced.
- Use a thermal protection thermostat.
- Do not operate an additional capacity controller.
-Oilreturnatlowfrequencymustbeguaranteed.
-ConsultationwithGEABock.
For operation with capacity regulator:
- The suction gas superheat temperature may need to be
reduced or set individuallywhen operating near to the threshold.
Whenoperatinginthevacuumrange,thereisadangerofair
enteringonthesuctionside.Thiscancausechemicalreactions,
a pressure rise in the condenser and an elevated compressed-
gas temperature. Prevent the ingress of air at all costs!
3.3 Operating limits
INFO!
Forrefilling,werecommendtheaboveoiltypes.
Alternatives: seelubricantstable,Chapter7.5.
The oil level must be in the
visible part of the sight
glass; damage to the com-
pressor is possible if over-
filled or underfilled!
ATTENTION!
max.
min.
0,8 Ltr.
oil level
Fig. 4
~
~