D GB F E GEA Bock Compressor HG34e A 96191-11.
About these instructions Read these instructions before assembly and before using the compressor. This will avoid misunderstandings and prevent damage. Improper assembly and use of the compressor can lead to serious or fatal injury. Observe the safety instructions contained in these instructions. These instructions must be passed onto the end customer along with the unit in which the compressor is installed.
96191-11.2014-DGbFE Contents 1 1.1 1.2 1.3 1.4 2 2.1 2.2 2.3 3 3.1 3.2 3.3 4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 5 5.1 5.2 5.3 5.4 5.5 5.6 5.7 6 6.1 6.2 6.3 6.4 6.5 6.6 6.7 7 7.1 7.2 7.3 7.4 7.5 7.
1| Safety 1.1 Identification of safety instructions: DANGER! Indicates a dangerous situation which, if not avoided, will cause immediate fatal or serious injury. WARNING! Indicates a dangerous situation which, if not avoided, may cause fatal or serious injury. CAUTION! Indicates a dangerous situation which, if not avoided, may cause fairly severe or minor injury. ATTENTION! Indicates a situation which, if not avoided, may cause property damage.
1| Safety 1.4 Intended use These assembly instructions describe the standard version of the HG34e A manufactured by GEA Bock. The compressor is intended for use in refrigeration systems in compliance with the limits of application. Only the refrigerant specified in these instructions may be used.
2 | Product description 2.1 Short description • Semi-hermetic four-cylinder reciprocating compressor with oil pump lubrication. • Lightweight aluminum design • Suction gas-cooled drive motor Transport eyelet Discharge shut-off valve 6 D Oil pump GB 1 2 3 4 7 8 9 10 11 12 13 Name plate 5 Oil sightglass F E Fig. 1 Cylinder cover Terminal box Valve plate Motor part Suction shut-off valve Fig. 2 Dimension and connection values can be found in Chapter 9 6 96191-11.
2 | Product description 2.2 Name plate (example) GEA Bock GmbH 72636 Frickenhausen, Germany HGX34e/380-4 SA AT38125A028 31,2/18,0A 132A 76A 19/28 1 2 3 4 5 6 7 8 9 10 11 12 13 33,1 27,3 39,7 32,8 SE SE 55 55 IP66 Fig. 3 1 2 3 4 5 Type designation Machine number maximum operating current Starting current (rotor blocked) ND LP: max. admissible operating pressure Low pressure side HD (HP): max. admissible operating pressure.
3 | Areas of application 3.1 Refrigerants • HFKW / HFC: • (H)FCKW / (H)CFC: R134a, R404A, R507, R407C R22 3.2 Oil charge The compressors are filled with the following oil type at the factory: - for R134a, R404A, R507, R407C FUCHS Reniso Triton SE 55 - for R22 FUCHS Reniso SP 46 Compressors with ester oil charge (FUCHS Reniso Triton SE 55) are marked with an X in the type designation (e.g. HGX34e/380-4 A). D INFO! For refilling, we recommend the above oil types.
R134a Fig. 5 R407C D Unlimited application range GB F Supplementary cooling or reduced suction gas temperature Fig. 6 E Supplementary cooling and reduced suction gas temperature Motor version S (more powerful motor) R404A/R507 Evaporating temperature (°C) Condensing temperature (°C) Suction gas superheat (K) Suction gas temperature (°C) Fig. 7 Max. permissible operating pressure (LP/HP)1): 19/28 bar 96191-11.2014-DGbFE 1) R22 Fig.
4 | Compressor assembly INFO! New compressors are factory-filled with inert gas (3 bar nitrogen). Leave this service charge in the compressor for as long as possible and prevent the ingress of air. Check the compressor for transport damage before starting any work. 4.1 Storage and transport Fig. 9 ? Storage at (-30°C) - (+70°C), maximum permissible relative humidity 10% - 95%, no condensation Do not store in a corrosive, dusty, vaporous atmosphere or in a combustible environment. Use transport eyelet.
4 | Compressor assembly 4.3 Maximum permissible inclination ATTENTION! Poor lubrication can damage the compressor. Respect the stated values. A a a A A GEA Bock GmbH 72636 Frickenhausen, Germany Fig. 14 a a A A max. 30°, max. 2 minutes a max. 15°, continuous operation 4.4 Pipe connections Fig. 15: Stepped internal diameters The discharge and suction line valves have stepped internal diameters so that pipes with standard millimetre and inch dimensions can be used.
4 | Compressor assembly 4.5 Pipes Pipes and system components must be clean and dry inside and free of scale, swarf and layers of rust and phosphate. Only use air-tight parts. Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being cracked and broken by severe vibrations. Ensure a proper oil return. Keep pressure losses to an absolute minimum. 4.
4 | Compressor assembly 4.7 Operating the shut-off valves Before opening or closing the shut-off valve, release the adjustable valve spindle seal by approx. ¼ of a turn counter-clockwise. After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise. Release Tighten Valve spindle seal Fig. 18 Fig. 17 4.
5| Electrical connection 5 Electrical connection DANGER! INFO! High voltage! Risk of electric shock! Only carry out work when the electrical system is disconnected from the power supply! onnect the compressor motor in accordance with the circuit diagram C (see inside of terminal box). Use suitable cable entry point of the correct protection type (see name plate) for routing cables into the terminal box. Insert the strain reliefs and prevent chafe marks on the cables.
5| Electrical connection The compressor is designed with a motor for star-delta circuits. Designation on the name plate Sticker on the terminal box Niedere Spannung Low voltage Bas voltage ∆ ∆/Y Star-delta start-up is only possible in the ∆ voltage range.
5.
A1 Alarm Motor protection A2 Overheating R1, R2 A3 Alarm high pressure XSS Terminal strip in the external switch cabinet D GB F E 96191-11.
5| Electrical connection 5.4 Electronic trigger unit MP 10 The compressor motor is fitted with cold conductor temperature sensors (PTC) connected to the electronic trigger unit MP 10 in the terminal box. Readiness to operate is signaled by the H3 LED (green) after the power supply is applied. In case of excess temperature in the motor winding, the unit switches off the compressor and the H1 LED illuminates red.
5 | Electrical connection 5.6 External connection of the MP 10 for terminal boxes at reduced height (Accessories) 0,5 mm² X3: 2 1 PTC1 PE 3 3 4 4 PTC2 Terminal box Fig. 23 R2 D 5.7 Function test of the trigger unit MP 10 GB Before start-up, troubleshooting or making changes to the control power circuit, check the functionality of the trigger unit: 96191-11.
6| Commissioning 6.1 Preparations for start-up INFO! To protect the compressor against inadmissible operating conditions, high pressure and low pressure pressostats are mandatory on the installation side. The compressor has undergone trials in the factory and all functions have been tested. There are therefore no special running-in instructions. Check the compressor for transport damage! 6.2 Pressure strength test DANGER! Bursting! The compressor must only be pressurised using nitrogen (N2).
6 | Commissioning 6.5 Refrigerant charge CAUTION! Wear personal protective clothing such as goggles and protective gloves! Make sure that the suction and discharge line valves are open. With the compressor switched off, add the liquid refrigerant directly to the condenser or receiver, breaking the vacuum.
7 | Maintenance 7.1 Preparation WARNING! Before starting any work on the compressor: Switch off the compressor and secure it to prevent a restart. Relieve compressor of system pressure. Prevent air from infiltrating the system! After maintenance has been performed: Connect safety switch. Evacuate compressor. Release switch lock. 7.2 Work to be carried out Oil change: In principle, an oil change is not mandatory if the system is correctly manufactured and operated.
7 | Maintenance 7.5 Extract from the lubricants table The oil type filled as standard in the factory is marked on the name plate. This oil type should be used as a preference. Alternatives are stated in the extract from our lubricants table below. Refrigerants HFKW (z.B. R134a, R407, R 404A) HFCKW (z.B.
33,1 / 39,7 33,1 / 39,7 HG34e/380-4 A HG34e/380-4 S A 220-240 V ∆ / 380-420 V Y - 3 - 50 Hz 265-290 V ∆ / 440-480 V Y - 3 - 60 Hz 4,8 14,0 / 8,1 31,2 / 18,0 26,1 / 15,1 25,5 / 14,7 21,1 / 12,2 21,1 / 12,2 17,0 / 9,8 96191-11.2014-DGbFE 11,1 9,3 8,9 7,4 7,2 6,0 6,0 kW A 18,3 / 10,5 ∆/ Y 2 59 56 60 57 57 54 48 55 kg Weight 22 (7/8) mm (inch) Discharge line DV 4 28 (11/8) mm (inch) Suction line SV Connections 1,3 Ltr.
9 | Dimensions and connections ca.285 ca.285 ca.285 DV B1DV B1 DV B1 Centre of gravity 46 46 46 79 A A B,L B,L B,L E F E E F F ca.315* 273 ca.315* 115 273 ca.315* 273 115 115 ca.135 ca.135 ca.135 A ca.190 ca.190J J ca.190 310 310 J 310 419 79 419 79 419 ca.540 ca.540 ca.540 H,D1 H,D1 H,D1 K,O K,O K,O 4x 12 4x 12 4x 12 230 230 272 230272 272 30 20 30 20 30 20 Anti-vibration pad A A A1 A A1 A1 1) SV 1) SV SV 1) M10 M10 40M10 40 40 D GB F 96191-11.
10| Declaration of conformity and installation DECLARATION OF CONFORMITY CE 08 for using the compressors within the European Union (in accordance with Low Voltage Directive 2006/95/EC) We hereby declare that the following refrigerating compressors Product designation: HG34e A comply with the Low Voltage Directive 2006/95/EC.
11| Service Dear customer, GEA Bock compressors are top-quality, reliable and service-friendly quality products. If you have any questions about installation, operation and accessories, please contact our technical service or specialist wholesaler and/or our representative. The GEA Bock service team can be contacted by phone with a toll-free hotline 00 800 / 800 000 88 or via e-mail: refrigeration@gea.com Yours faithfully GEA Bock GmbH Benzstraße 7 72636 Frickenhausen Germany D GB F 96191-11.
We live our values. Excellence • Passion • Integrity • Responsibility • GEA-versity GEA Group is a global engineering company with multi-billion euro sales and operations in more than 50 countries. Founded in 1881, the company is one of the largest providers of innovative equipment and process technology. GEA Group is listed in the STOXX® Europe 600 index. D GB F GEA Bock GmbH Benzstraße 7, 72636 Frickenhausen, Germany Telephone: +49 7022 9454-0, Fax: +49 7022 9454-137 refrigeration@gea.com, www.gea.