4| Compressor assembly
INFO! Newcompressorsarefactory-lledwithinertgas(3barnitrogen).
Leave this service charge in the compressor for as long as possible
and prevent the ingress of air.
Check the compressor for transport damage before starting any
work.
The pipe connections have graduated inside diameters so that pipes with
standart millimetre and inch dimensions can be used.
The connection diameters of the shut-off valves are rated for maximum
compressor output. Theactualrequiredpipecrosssectionmustbe
matched to the output. The same applies for non-return valves.
4.3 Pipe connections
ATTENTION! Do not solder as long as the compressor is under pressure.
Superheating can damage the valve. Remove the pipe supports
therefore from the valve for soldering and accordingly cool the
valve body during and after soldering.
Only solder using inert gas to inhibit oxidation products (scale).
?
4.1 Storage and transport
Use transport eyelet.
Do not lift manually!
Use lifting gear!
Storageat(-30°C)-(+70°C),maximumpermissiblerelativehumidity
10% - 95%, no condensation
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Fig. 10
Fig. 9
ATTENTION! Attachments(e.g.pipeholders,additionalunits,fasteningparts,
etc.) directly to the compressor are not permissible!
4.2 Setting up
Setuponanevensurfaceorframewithsufcientload-
bearing capacity.
Single compressor preferably on vibration damper.
Duplex and parallel circuits always rigid.
Provideadequateclearanceformaintenancework.
Ensureadequatecompressorventilation.
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment.
Fig. 11
Fig. 12
Fig. 13
Fig.14:graduated
internal diameter