3| Areas of application
ATTENTION! Compressor operation is possible within the operating limits
shown in the diagrams. Please note the signicance
of the shaded areas. Thresholds should not be selected as design
or continuous operation points.
- Permissible ambient temperature (-20°C) - (+60°C)
- Max. permissible discharge end temperature 140 °C
-Max.permissibleswitchingfrequency8x/h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
Foroperationwithfrequencyconverter:
- The maximum current and power consumption must not be
exceeded. Inthecaseofoperationabovethemainsfrequency,
the application limit can therefore be limited.
Thecompressorsarelledatthefactorywiththefollowingoiltype:
GEABockC85E(onlythisoilmaybeused)
3.1 Refrigerants
• CO
2
: R744
3.2 Oil charge
3.3 Limits of application
Evaporation temperature (°C)
Condensing temperature (°C)
Suction gas superheat (K)
Suction gas temperature (°C)
Fig. 5
Max. permissible operating
pressure (LP/HP)
1)
: 40/55 bar
1)
LP = Low pressure
HP = High pressure
R744
Unlimited
application range
The oil level must be in the
visible part of the sight
glass; damage to the com-
pressor is possible if over-
filled or underfilled!
ATTENTION!
max.
min.
0,7 Ltr.
oil level
Fig. 4
~
~