Manual

24
D
GB
F
E
09917-02.2015-DGbFEI
8| Technical data
Type
No. of cylinders
Displacement
50 / 60 Hz
(1450/1740
rpm)
Electrical data
Weight
Connections Oil
charge
Voltage Max.
Operating
current
/ Y
Max. power
consump
-
tion
Starting
current
(rotor
locked)
/ Y
Dis-
charge
line
DV
Suction
line
SV
m
3
/h A kW A kg mm (inch) mm (inch) Ltr.
HGX12P/30-4 CO
2
2
2,8 / 3,4 5,9 / 3,4 1,8 40 / 23 53
12 (
1
/
2
) 16 (
5
/
8
) 0,8
HGX12P/40-4 CO
2
3,6 / 4,4 7,3 / 4,2 2,3 43 / 25 53
HGX12P/50-4 CO
2
4,5 / 5,4 8,7 / 5,0 2,9 43 / 25 53
HGX12P/60-4 CO
2
5,4 / 6,4 9,5 / 5,5 3,2 45 / 26 49
HGX12P/75-4 CO
2
6,7 / 8,1 10,6 / 6,1 3,6 45 / 26 49
1
2
3
2
4
220-240 V / 380-420 V Y - 3 - 50 Hz
265-290 V / 440-480 V Y - 3 - 60 Hz
Tolerance (± 10%) relative to the mean value of the voltage range.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
 For60Hzoperation,thespecicationshavetobemultipliedbythefactor
1.2. The max. working current remains unchanged.
- Take account of the max. operating current / max. power consumption for
design of fuses, supply lines and safety devices.
Fuse: Consumption category AC3
1
2
3
4
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections