6.8 Avoid slugging
ATTENTION! Slugging can result in damage to the compressor and cause
refrigeranttoleak.
To prevent slugging:
The complete refrigeration plant must be properly designed.
All components must be compatibly rated with each other with regard to output (particularly the
evaporator and expansion valves).
Suction gas superheating at the compressor input should be > 10 K (check the setting of the
expansion valve).
Thesystemmustreachastateofequilibrium.
Particularlyincriticalsystems(e.g.severalevaporatorpoints),measuressuchastheuseofliquid
traps,solenoidvalveintheliquidline,etc.arerecommended.
There should be no movement of refrigerant in the compressor while the system is at a
standstill.