Operation mode: The oil sump heater operates when the compressor is shut down.
The oil sump heater is switched off when the compressor starts.
Connexion: The oil sump heater must be connected via an auxiliary contact (or parallel wired auxiliary
contact) of the compressor contactor to a seperate electric circuit.
Electricaldata:110-240V-1-50/60Hz,50-120W,PTC-heateradjusting.
5| Electrical connection
The compressor and the trigger unit MP10 are operational when the H3 LED (green) lights.
5.6 Function test of the trigger unit MP 10
Pos
Procedure
LED H1 LED H2 LED H3
red red green
1
Interrupt power supply (L1 or S1) OFF OFF OFF
Release the motor temperature sensor connection (1 or 2)
Release the hot gas temperature sensor (if installed) (3 or 4)
2
Restore the power supply (L1 or S1) ON
Function check of motor temperature sensor: operational ON
Function check of hot gas temperature sensor: operational ON
3
Interrupt power supply again (L1 or S1) OFF OFF OFF
Reconnect terminals 1 or 2 and/or 3 or 4
4
Restore the power supply (L1 or S1): OFF OFF ON
MP 10 is operational again
Before start-up, troubleshooting or making changes to the control power circuit, check the functionality
of the trigger unit:
ATTENTION! The oil sump heater must generally be connected and operated.
5.8 Ventilator motor
The ventilator motor for cooling the compressor is already wired in the terminal box. Please consult
the main-line wiring diagram in the terminal box for the power supply and triggering via the com-
pressor contactor. The ventilator motor is protected by a pressure controller.
Electricaldata:230V/1/50...60Hz,140W,0,71A
5.7 Oil sump heater (accessories)
Inordertoavoiddamagetothecompressor,thecompressormustbeequippedwithanoilsump
heater.