User Manual
10
D
GB
F
E
96031-02.2015-DGbF
4| Compressor assembly
4.4 Flange shut-off valves (HP/LP)
ATTENTION! The compressor must be depressurised through connections A
andBbeforecommencinganyworkandpriortoconnectingtothe
refrigerant system.
Fig. 11
Fig. 12
4.5 Operatingmodeofthelockableserviceconnections
Pipe connection
Opening the shut-off valve:
Spindle: turn to the left (counter-clockwise) as far as it will go.
—> Shut-off valve completely opened / service connection closed.
The connection which cannot be shut off is intended for safety devices.
Opening the service connection
Spindle: Turn ½ - 1 turn to the right clockwise.
—> Service connection opened / shut-off valve opened.
The connection which cannot be shut off is intended for safety devices.
Spindle
Connection cannot
be shut offConnection
blocked
Service connec
-
tion closed
Pipe connection
Spindle
Connection cannot
be shut offConnection
offen
Service connec
-
tion opened
Fig. 13
Fig. 14
A
B
Afteractivatingthespindle,generallytthespindleprotectioncapagainandtightenwith14-16Nm.
This serves as a second sealing feature during operation.