5| Electrical connection
ATTENTION!
Terminals1-6onthetrigger
unit MP 10 and terminals PTC
1andPTC2onthecompres-
sor terminal board must not
comeintocontactwithmains
voltage.Thiswoulddestroythe
trigger unit and PTC sensors.
ThesupplyvoltageatL1-N
(+/- for DC 24 V version) must
beidenticaltothevoltageat
terminals11,12,14and43.
5.6 Electronic trigger unit MP 10
The compressor motor is tted with cold conductor temperature sensors (PTC) connected to the
electronic trigger unit MP 10 in the terminal box. Readiness to operate is signalled by the H3 LED
(green) after the power supply is applied. In the case of excess temperature in the motor winding, the
unit switches off the compressor and the H1 LED lights red.
The hot gas side of the compressor can also be protected against overtemperature using a thermal
protection thermostat (accessory). The H2 LED (red) is provided for the protection function.
Theunittripswhenanoverloadorinadmissibleoperatingconditionsoccur.Findandremedy
thecause.
5.7 ConnectionofthetriggerunitMP10
INFO!
Theunithasarestartpreventiondevice.Afteryouhaverectiedthe
fault,interruptthemainsvoltage.Thisunlockstherestartprevention
deviceandtheLEDsH1andH2goout.
INFO! ConnectthetriggerunitMP10inaccordancewiththecircuitdia-
gram.Protectthetriggerunitwithadelayed-actionfuse(F)ofmax.
4A.Inordertoguaranteetheprotectionfunction,installthetrigger
unitastherstelementinthecontrolpowercircuit.
Temperature monitoring connections:
Motor winding: Terminals 1 - 2
Thermal protection thermostat: Terminals 3 - 4
Restart prevention: Terminals 5 - 6
Fig. 19
Terminal board