4.5 Laying suction and pressure lines
INFO! Proper layout of the suction and pressure lines directlyafter the
compressorisintegraltothesmoothrunningandvibrationbehaviour
ofthesystem.
ATTENTION! Improperlyinstalled pipes can cause cracks and tears which can
resultinalossofrefrigerant,
Aruleofthumb:
Alwayslaytherstpipesectionstartingfromtheshut-offvalvedownwardsand
paralleltothedriveshaft.
4| Compressor assembly
4.4 Pipes
Pipes and system components must be clean and dry inside and free of scale, swarf and layers of
rust and phosphate. Only use air-tight parts.
Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being
cracked and broken by severe vibrations.
Ensure a proper oil return.
Keep pressure losses to an absolute minimum.
ATTENTION! Superheatingcandamagethevalve.
Removethepipesupportsfromthevalveforsoldering.
Onlysolderusinginertgastoinhibitoxidationproducts(scale).
4.3 Pipe connections
The pipe connections have graduated inside diameters so that pipes with
standart millimetre and inch dimensions can be used.
The connection diameters of the shut-off valves are rated for maximum
compressor output. Theactualrequiredpipecrosssectionmustbe
matchedtotheoutput.Thesameappliesfornon-returnvalves.
Fig. 11: graduated
internal diameter
Fig. 12
Asshortas
possible
Rigid
fixed point