User Manual
D
GB
F
E
I
Ru
27
09911-01.2015-DGbFEIRu
8| Technical data
Type
No. of cylinders
Displace-
ment
50 / 60 Hz
(1450 / 1740
rpm)
Electrical data
Weight
Connections
Oilcharge
Sound
pressure
level
Voltage Max.
Operating
current
PW 1 + 2
Max.
power
consump
-
tion
Starting
current
(rotorlocked)
PW 1 / PW 1 + 2
Discharge
line
DV
Suction
line
SV
m
3
/h A kW A kg mm (inch) mm (inch) Ltr. dB(A)
HA5/725-4
4
62,9 / 75,5 26 12,5 107 / 140 204
28 (1
1
/
8
) 42 (1
5
/
8
) 4,5
72 / 70
HA5/830-4 72,2 / 86,7 26 12,8 126 / 160 207 73 / 71
HA5/945-4 82,2 / 98,6 26 12,9 126 / 160 205 73 / 71
1
2
3
2
4
380-420VY/YY-3-50HzPW
440-480VY/YY-3-60HzPW
PW = Part Winding
Winding ratio : 66% / 33%
L / M
5
Tolerance (± 10%) relative to the mean value of the voltage range.
Othervoltagesandtypesofcurrentonrequest.
-Thespecicationsformax.powerconsumptionapplyfor50Hzoperation.
For60Hzoperation,thespecicationshavetobemultipliedbythefactor
1.2. The max. working current remains unchanged.
- Take account of the max. operating current / max. power consumption for
design of fuses, supply lines and safety devices. Fuse: Consumption
category AC3
1
2
Allspecicationsarebasedontheaverageofthevoltagerange
For solder connections
L = low temperature (-35 / 40 °C), M = normal cooling (-10 / 45 °C),
soundpressurelevelmeasuredinlowreectionmeasuringarea,
measuring distance 1m.
Compressor operation at 50 Hz (1450 rpm), refrigerant R404A.
Valuesstatedareaveragevalues,tolerance±2dB(A).
5
3
4