3| Areas of application
ATTENTION! Compressor operation is possible within the operating limits
shown in the diagrams. Please note the signicance
of the shaded areas. Thresholds should not be selected as design
or continuous operation points.
- Max. permissible ambient temperature 45 °C
- Max. permissible discharge end temperature 140 °C
-Max.permissibleswitchingfrequency8x/h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
Foroperationwithfrequencyconverter:
- The maximum current and power consumption must not be
exceeded.Inthecaseofoperation abovethemains frequency,
the application limit can therefore be limited.
When operating in the vacuum range, there is a danger of air
enteringonthesuctionside.Thiscancausechemicalreactions,
a pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!
Thecompressorsarelledatthefactorywiththefollowingoiltype:
- for R404A/R507 FUCHS Reniso Triton SE 55
- for R22 FUCHS Reniso SP 46
Compressorswithesteroilcharge(FUCHSRenisoTritonSE55)aremarkedwithanXinthetype
designation (e.g. HAX12P/110-4).
3.1 Refrigerants
• HFKW/HFC: R404A/R507
• (H)FCKW/(H)CFC: R22
3.2 Oil charge
3.3 Limits of application
INFO!
Forrefilling,werecommendtheaboveoiltypes.
Alternatives: seelubricantstable,Chapter7.5.
The oil level must be in the
visible part of the sight
glass; damage to the com-
pressor is possible if over-
filled or underfilled!
ATTENTION!
max.
min.
0,5 Ltr.
oil level
Fig. 4
~
~