User Manual
20
D
GB
F
E
I
Ru
09651-12.2014-DGbFEIRu
7.1 Preparation
7.2 Worktobecarriedout
7| Maintenance
In order to guarantee optimum operational reliability and service life of the compressor, we recommend
carryingoutservicingandinspectionworkatregularintervals:
Oil change:
- not mandatory for factory-produced series systems.
- foreldinstallationsorwhenoperatingneartheapplicationlimit:forthersttimeafter100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Dispose of used oil according to the regulations; observe national regulations.
Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of
auxiliary devices such as oil sump heater, pressure switch.
WARNING! Beforestartinganyworkonthecompressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Preventairfrominltratingthesystem!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Releaseswitch-onlock.
6.8 Connection of oil level regulator
The connection "O" is provided for installing an oil level regulator. A corresponding adapter must be
obtained from the trade.
6| Commissioning
OnlyusegenuineGEABockspareparts!
7.3 Spare parts recommendation
HA12P / ...
60-4 75-4 90-4 110-4
Designation
Ref. No. Ref. No. Ref. No. Ref. No.
Set of gaskets 80339
Valve plate kit 80352 80353
Oil pump kit 08324