7| Accessories
7.1 Capacity regulation
FK50 / ... ... N + TK ... K
Designation Item No. Item No.
Specialaccessory12V 08703 08708
Specialaccessory24V 08704 08709
Foradescription,seetechnicalinformation"Capacityregulation"(ItemNo.09900)
Ifthecapacityregulatorisfactory-tted,itisintegratedintoanextra,dedicatedcylindercover.For
retrots,itissuppliedwiththecylindercover.Theregulatorclosesonecylinderbankatatime(capacity
regulationapprox.33%).Tworetrotkitsarerequiredforacapacityregulationofapprox.66%.
Ascrew-inoptionisprovidedforthesensorelementonthehotgassideofthecompressor
housing(seeChap.9).Connectthethermalprotectionthermostatinserieswiththecontrolline.
TechnicalData:
Switchingvoltagemax. : 24VDC
Switchingcurrentmax. : 2.5Aat24VDC
Switch-offtemperature : 145°C±5K
Switch-ontemperature : approx.115°C
7.2 Thermal protection thermostat (Item No. 07595)
ATTENTION! Capacity-regulated operation alters the gas speeds and pressure
ratiosoftherefrigeratingplant:Adjustthesuctionlineroutingand
dimensioning accordingly, do not set the control intervals too close and
do not let the system switch more than 12 times per hour (refriger-
atingplantmusthavereachedastateofequilibrium).Continuous
operation in the control stage is not recommended as the gas
velocity in the plant system under certain circumstances does not
guaranteesufcient oil return tothecompressor with activated
capacity regulator for a compressor speed below 1200 - 1500 rpm.
We recommend switching to unregulated operation (100% capacity)
for at least 5 minutes per capacity-regulated operating hour. An
assuredoilreturncanalsoberealisedbya100%capacityrequire-
ment after each compressor restart as otherwise the compressor
can also be shut down in the regulated operating time by the
thermostat.
Electricalactuationofthesolenoidvalve:Normallyopen,(corre-
sponds to 100 % compressor capacity).
Cylinder covers for capacity regulation are marked with the
designation "CR" (Capacity Regulator).