3 | Areas of application
ATTENTION! Compressor operation is possible within the limits of application
showninthediagrams.Pleasenotethesignicance
of the shaded areas. The limits of application must
be observed. Thresholds should not be selected as design
or continuous operating points.
-Max.permissibledischargeendtemperature:140°C
-Max.permissibleambienttemperature:100°C
-Max.permissibleswitchingfrequency:12x/h
-Aminimumrunningtimeof2min.atequilibrium(continuous
operation) must be achieved.
Avoid continuous operation near the threshold. Should the
compressor happen to be used near the thresholds, we
recommend the use of a thermal protection thermostat
(Accessories,Chap.7).
When operating in the vacuum range, there is a danger of air
entering on the suction side. This can cause chemical reactions,
a pressure rise in the condenser and an elevated compressed-
gas temperature. Prevent the ingress of air at all costs!
The compressors are factory-lled with the following oil type:
- for R134a, R404A/R507, R407C FUCHS Reniso Triton SE 55
- for R22 FUCHS Reniso SP 46
Compressors with ester oil charge (FUCHS Reniso Triton SE 55) are marked with an X in the type
designation (e.g. FKX30/325 N).
3.1 Refrigerants
HFKW / HFC: R134a, R404A/R507, R407C
(H)FCKW / (H)CFC: R22
3.2 Oil charge
3.3 Limits of application
INFO!
Forrecharging,werecommendtheaboveoiltypes.Alternativesare:
see lubricants table , Chapter 6.5.