5| Commissioning
5.7 Avoidingliquidshocks
ATTENTION! Slugging can damage the compressor and cause refrigerant to
leak.
Topreventliquidshocks:
Thecompleterefrigerationplantmustbecorrectlydesignedandexecuted.
Thecapacitiesofallcomponentsmustbecompatible(particularlyevaporator
andexpansionvalve).
Suctiongassuperheatingattheevaporatoroutputshouldbeatleast7 10K(checksetting
oftheexpansionvalve).
Thesystemmustreachastateofequilibrium.
Particularlyincriticalsystems(e.g.severalevaporatorpoints),suitablemeasures,e.g.
useofliquidtraps,solenoidvalveintheliquidline,etc.arerecommended.