Instruction Manual

D
GB
F
E
21
96246-07.2014-DGbRu
6| Maintenance
6.6 Decommissioning
6.5 Excerpt from the lubricant table
Theoilgradelledasstandardinthefactoryisnotedonthename plate. This oil grade should be
used preferably. Alternatives to this are listed in the following excerpt from our lubricant table.
Refrigerant Bockseriesoilgrades
Recommended alternatives
HFKW
(e.g.
R134a,
R404A/R507,R407C)
Fuchs Reniso Triton SE 55
FUCHS Reniso Triton SEZ 32
ICI Emkarate RL 32 H, S
MOBIL Arctic EAL 32
SHELL Clavus R 32
HFCKW
(e.g.
R22)
Fuchs Reniso SP 46
FUCHS Reniso, z.B. KM, HP, SP 32
SHELL Clavus SD 22-12
TEXACO Capella WF 46
Informationonfurthersuitableoilsonrequest.
Close the shut-off valves on the compressor. Drain the refrigerant (it must not be discharged into the
environment)anddisposeofitaccordingtotheregulations.Whenthecompressorisdepressurised,
undo the fastening screws of the shut-off valves. Remove the compressor using an appropriate hoist.
Dispose of the oil inside in accordance with the applicable national regulations.