User Manual

13
D
GB
F
E
09794-05.2012-DGbFEI
Messages and emergency operation
Oil pressure too low
LED ON / Compressor OFF
Switch 4 Off
Reset
Reset
4
Fault message
Compressor starts up immedi-
ately.
LED OFF
Compressor starts up through
machine control. LED ashes
Fault message
Combined function 2:
Compressor not turning.
LED ON / Compressor OFF
5 + 6 are bridged. Compressor
starts up through machine control.
LED ashes
Switch 5 Off
Reset
Reset
5
6
Only 6 is bridged. Compressor
starts up through machine control.
LED OFF
Switch 6 Off
Reset
Surge op. too high
LED ON / Compressor ON
Switch 7 Off
Reset
Reset
Information message
7
LED OFF
Reset to „0“
Counting starts again
12 starts per hour
exceeded
Recommended oil change
LED ON / Compressor ON
Switch 8 Off
Reset
Reset
Information message
8
LED OFF
Reset to „0“
Evaluation starts again
Combined function 1:
Liquid at start
LED ON / Compressor OFF
Display a) Reset to initial function b)
Function bridged (emergency
operation - no safety function)
Compressor starts up
immediately.
LED OFF
Compressor starts up through
machine control. LED ashes
Compressor starts up through
machine control. LED ashes
Reset
Compressor starts up
after fault eliminated.
LED OFF
Fault message
Engine monitoring by win-
ding temperature feeler
+
+
+
+
+