Technical Specifications

83
Setup Wizard Selections
SVI II AP Monitor Screen
Setup Wizard Selections
After you start the Setup Wizard Figure 57 appears where you can select the setup features
to perform:
Figure 57 Setup Wizard Selections
Setup Wizard Step 1
When selected, the device Tag, Long Tag (HART 6 only), Descriptor, and Message are
modified.
Setup Wizard Step 2
When selected you can set the air action. You can also reset the configuration and
calibration parameters to factory defaults; Air Action, Travel, and PID (tuning) parameters.
Setup Wizard Step 3
When selected, you can perform a travel calibration. To determine valve position, the
positioner must measure the closed and open positions of the valve. The SVI II AP first
exhausts the actuator and measures the position, then fills the actuator and measures the
position. From these measurements the valve position can be determined.
Additionally, you can enter the expected Supply Pressure.