Technical Specifications

ValVue Digital Communications Software Ver. 2.80
80
GE Oil & Gas
3. Read the results below (Figure 55).
Figure 55 Send Command Results Displayed
List of Available HART Commands
When you click on the drop down arrow, ValVue displays the available HART commands. Scroll
through the list until you locate the command you wish to execute:
000 Read Identifier - Returns the unique identifier from the device including the device
ID, device type, and the manufacturers ID.
001 Read Primary Variable - Returns the position in percent open.
002 Read Current - Returns the input signal in mA.
003 Read All Variables - Returns the input signal and the position in percent open
011 Read ID from Tag - Prompts the user for a tag name. The tag name is sent in a
HART command and if received by a device with a matching tag name, the ID of the
device is returned. The format of the ID is the same as command 001 Read Identifier.
012 Read Message - Reads the message that was stored in the device when it was
configured
013 Read Tag & Descriptor - Reads the tag name, date, and the descriptor that was
stored in the device when it was configured
016 Read Assembly Number - Reads the final assembly number that was stored in the
device when it was assembled at the factory