What You Can Do on the Monitor
SVI II AP Monitor Screen
Positioner Operations
Signal Indicates the input analog signal expressed in % and in mA of the configured
signal range.
Position Indicates the actual valve position in % of valve opening. 0% is always closed
and 100% is open. Because the travel of a valve may exceed its nominal travel,
positions greater than 100% are possible (see “Open Stop Adjustment” on
page 61).
Setpoint In NORMAL mode, the setpoint is the target position based on the characterized
input. In MANUAL mode, it is the target position to which the SVI II AP is control-
ling the valve. The manual setpoint may be changed by dragging the lower
thumb on the position indicator.
Pressure The SVI II AP continuously monitors the actuator pressure and displays accord-
ing to the configured units (psi, bar, or kPa).
Position Indicator This shows the valve position graphically and consists of three parts:
The upper part contains an indicator showing the value of the input
signal. In Normal mode this is the position setpoint. WARNING! - In manual
mode, this is the position that the valve moves to if normal mode is selected.
The center green bar shows the valve position in percent. The numerical
valve position is shown in the center.
The lower part contains an indicator (that can be dragged when active)
showing the valve setpoint. In operating mode, this is the same as the sig-
nal. In manual mode it is the valve setpoint. You can drag the indicator to
change the valve setpoint. While dragging, the number in the center bar
shows the manual setpoint that is selected when you release the indicator.
Send Command
menu
Use this pulldown to send HART commands whose responses are seen in the
Send Command Display window.
Send Command
Display window
Displays results of HART commands.
Setup Wizard button Click to launch the Setup Wizard ( “Setup Wizard Selections” on
page 83).