Technical Specifications
643
Diagnostics Tab
Figure 13 Extended Actuator Signature
Perform Diagnostics Clicking Perform Diagnostics starts the selected diagnostic proce-
dure. When finished, the results appear in a graph and/or the diag-
nostics results box. A progress tab appears while the diagnostic
process is running.
View Saved Diag. Clicking View Saved Diag. allows you to view the results of a diag-
nostic test that had been saved earlier in a file. Actuator signatures
are saved when the SVI2 memory is saved (see the Monitor menu)
and all types of signature can be saved in a diagnostic file from the
Diagnostics menu.
Choose Signature Curve
Select Curve allows diagnostic graphs that have been saved previ-
ously to be displayed. Two graphs (plus the current graph if one
has just been run) may be displayed at once in order to compare
the results.
None - Removes the curve.
Current Signature - Displays the last run standard actuator
signature (note: the last run standard signature in the SVI is
lost if power to the SVI is lost).
Saved Signature - Displays the standard actuator signature
saved in the SVI (if any).
Baseline Signature - Displays the standard actuator
signature saved as the baseline signature in the SVI (if any).
Current Signature from dp1 File - Allows you to select a dp1
file for this or another SVI. The current standard actuator