Technical Specifications
623
Read Status
Read Status
To retrieve the fault codes:
1. Select Read Status from the drop down list.
2. Click Send. The results appear in the lower left box. The fault codes also appear on the
Status page.
The status block also contains other status codes returned by HART. These include
Configuration Change, Device malfunction, and Variable out of limits.
Menu - Monitor
When you right-click on the Monitor tab, a context menu appears. The items that appear
depend on the SVI2 mode:
Full Open - Moves the valve to full open. This command work by taking the valve out
of closed loop control and send a high or low signal to the I/P. This is available only in
manual or setup mode.
Full Closed - Moves the valve to full closed. This command work by taking the valve
out of closed loop control and send a high or low signal to the I/P. This is available
only in manual or setup mode.
Set to Fail Position - Moves the valve full open or full closed, whichever is the fail
position of the actuator.
Cancel Transfer - Returns the SVI2 to manual mode from the bumpless transfer
mode. Available during a bumpless transfer.
Reset - Selecting this issues a master reset to the device, causing it to go through its
startup routine and re-initializing all of its operating parameters from non-volatile
memory.
Report Setup - Allows you to select a report file and a report printing program.
Report - Generates a report of the SVI2 parameters.
Save SVI Data - Saves the SVI2 internal parameters to a disk file that can be read by
the ValVue.
Restore SVI Data - Reads data that has been saved with a Save SVI Data command
and sends HART commands to set the positioner to match the data that was read.
This can be used to clone an SVI into a new SVI. Note: items like tag, which should be
unique, and position calibrations which differ on each positioner are not cloned. This
command is available only in manual mode.
Detach Trend - Removes the trend display from the tabbed dialog and creates a
separate trend display.
Help - Displays the help file at the Monitor tab instructions.