Technical Specifications
609
Controller Settings Tab
Controller Settings Tab
From the Controller Settings tab you can change the parameters that control the process
controller.
Figure 22 Controller Settings Tab
Fields
Derivative Source Determines whether a change in process variable or a change in
error (setpoint- process variable) causes derivative action.
Setpoint Tracking If setpoint tracking is selected, when the controller is changed from
the Manual mode to Local mode, the setpoint is set to equal the
current process variable. In that case the process is not upset by
the change from manual to local.
Freeze on Bad Value If selected and if the process variable read from the auxiliary input
channel is not a valid reading, the controller output is not changed.
Alarm Status
The alarm status indicates when the process variable
is
outside
of
the
user specified range
of
upper alarm limit and lower alarm
limit
.
The alarm can
be
specified
as
an absolute range
or as a
deviation from
setpoint.